4-Line Filters for Installations and Systems
Power line filters for three-phase systems with additional LF suppression R...
4-Line Filters for Installations and Systems
Power line filters for three-phase systems with additional LF suppression Rated
voltage 440/250 V~, 50/60 Hz Rated current 12 A Construction
s Four-line filter s Metal case
B84134-F
Features
s Compact design
Applications
s Switch-mode power supplies for traction s Industrial installations, computers
Terminals
s Tab connectors 6,3 × 0,8 mm
Marking
www.DataSheet4U.com
Marking on component: Manufacturer’s logo, ordering code, rated
voltage, rated current, date code Minimum marking on packaging: Manufacturer’s logo, ordering code Circuit diagram
LINE L1 LOAD L1 ’
L2
L2 ’
L3
L3 ’
N
N’
SSB1067-G
301 03/01
4-Line Filters for Installations and Systems
Technical data Rated
voltage V R Rated current IR Test
voltage VP Leakage current I leak Climatic category 440/250 V~, 50/60 Hz referred to 40 °C ambient temperature 1414 V–, 2 s (line/line) 2700 V–, 2 s (lines/case) at 400 V~, 50 Hz
B84134-F
in accordance with EN 60068-1 25/085/21 (– 25 °C/+ 85 °C/21 days damp heat test)
Characteristics and ordering codes IR A 12 I leak mA Approx. weight 1,1 kg B84134-F12-A1 Ordering code Approvals
565-3
< 3,5
×
×
×
× = approval granted
Dimensional drawing
Terminals: Tab connectors 6,3 x 0,8mm
302 03/01
4-Line Filters for Installations and Systems
Insertion loss (typical values at Z = 50 Ω) unsymmetrical, adjacent branches terminated common mode, all branches in parallel (asymmetrical) differential mode (symmetrical) B84134-F12-A1
...