3-Line Filters Sine-Wave Output Filters
Sine-wave filters for three-phase systems Rated voltage 440/250 V~, 50/60 Hz Rat...
3-Line Filters Sine-Wave Output Filters
Sine-wave filters for three-phase systems Rated
voltage 440/250 V~, 50/60 Hz Rated current 6 to 35 A Construction
s Three-line filter s Metal case
B84143-V*-R27
Features
s s s s s
Easy to install Space-saving design Degree of protection: IP 201) Motor cables of more than 100 m possible Minimized motor noise and eddy current losses in the motor windings
Applications
s Sine-wave output filters for frequency converters in
variable speed drivers, solar systems, UPS Terminals www.DataSheet4U.com
s Safe-to-touch terminal blocks
Marking Marking on component: Manufacturer’s logo, ordering code, rated
voltage, rated current, rated temperature, date code Minimum marking on packaging: Manufacturer’s logo, ordering code Typical circuit diagram
Inverter Wechselrichter
U1 V1 W1
LOAD Last
U2 V2 W2
SSB1572-D
1) In accordance with IEC 60529:1989; EN 60529:1991; DIN VDE 0470-1
269 03/01
3-Line Filters Sine-Wave Output Filters
Technical data Rated
voltage V R Rated current I R Test
voltage VP Overload capability Converter output frequency fM Converter pulse frequency fP
Voltage drop (input to output) ∆V Power dissipation PV Capacitive reactive current Iq Climatic category 440/250 V~, 50/60 Hz
B84143-V*-R27
referred to 40 °C ambient temperature 1770 V–, 2 s (line/line) 2700 V–, 2 s (lines/case) 1,5 · IR for 1 min per hour 0 … 100 Hz 6 … 16 kHz at I R, 50 Hz typical value at 230 V, 50 Hz (typical value) 25/1005/21 (– 25 °C/+ 100 °C/21 days damp...