DC Current transducer DF-C10
For the electronic mesurement of low DC currents, with galvanic isolation between the prima...
DC Current transducer DF-C10
For the electronic mesurement of low DC currents, with galvanic isolation between the primary (High power) and the secondary circuits (Electronic circuit)
IPN = 10..500mA
Preliminary
Electrical data
Primary nominal current IPN (mA.t) 10 20 50 100 300 500 IO C VOUT Vc IC RL Vd Primary current range IP (mA.t) 16 38 80 160 480 800 Analogue Output signal VOUT (V) 0-10 0-10 0-10 0-10 0-10 0-10 30 ± 10 ± 12...15 20 ≥2 5000 Type
DF 0.01 C10 DF 0.02 C10 DF 0.05 C10 DF 0.1 C10 DF 0.3 C10 DF 0.5 C10 A.t V VDC mA kΩ VAC
Features
DC Measurement Low current transducer Panel mounting Bipolar
voltage supply Extended measuring range
Overload capacity Analog Output signal @ ± IPN Supply
voltage Current consumption (max) Load resistance Isolation test
voltage1)
Advantages
Large aperture Good performances in harsh EMC environment High isolation between primary and secondary circuits Easy to mount Bipolar No insertion losses
Accuracy-Dynamic performance data
X εL VOE VOT tr Accuracy2) of reading @± 12V, TA=25°C Linearity2) of IPN Electrical Offset
Voltage @ TA=25°C @IP=0 Thermal drift of VOE @ 0..+70° Response time @ 90% of I PN ±4 ± 0.8 ± 50 ± 100 <140 % % mV mV mS
General data
TA TS m Ambient operating temperature Ambient storage temperature Mass Standard 0..+70 -25..+85 140 TBD °C °C g
Applications
DC leakage current measurement Differential current measurement in DC applications Low DC current measurement
Options on request
N...