Current Transducers HAZ 4000..20000-SRU
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvan...
Current Transducers HAZ 4000..20000-SRU
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 4000..20000 A VOUT = 0-10 V (T-RMS DC)
Electrical data
Primary nominal r.m.s. current IPN (A) 4000 6000 10000 12000 14000 20000 Primary current measuring range IP (A) ± ± ± ± ± ± 4000 6000 10000 12000 14000 20000 Type
HAZ 4000-SRU HAZ 6000-SRU HAZ 10000-SRU HAZ 12000-SRU HAZ 14000-SRU HAZ 20000-SRU
Features
Hall effect measuring principle Galvanic isolation between primary
± 15 ± 30 30,000 > 1000 0-10 100 > 10 V mA A MΩ V DC Ω kΩ
www.DataSheet4U.com
VC IC IOC RIS VOUT ROUT RL
Supply
voltage (± 5 %) Current consumption Overload capacity Isolation resistance @ 500 VDC Output
voltage @ ± IPN, RL = 10 kΩ, TA = 25°C Output internal resistance approx. Load resistance
True-rms, 0-10V DC
voltage output Isolation
voltage 12kV Rms/ 50 Hz Low power consumption Package in PBT meeting UL 94-V0
/ 1 min
and secondary circuit
Advantages
Easy mounting Small size and space savings Only one design for wide current High immunity against external
interference ratings range
Accuracy - Dynamic performance data
X
ε
L
VOE VOH VOT TCε G tr f
Accuracy @ IPN, TA = 25°C (without offset) Linearity error 1) (0 .. ± IPN) Electrical offset
voltage, TA = 25°C, @ IP = 0 Hysteresis offset
voltage @ IP = 0; after an excursion of 1 x IPN Thermal drift of ...