OVERLOAD RELAY. 3RU1116-1GC1 Datasheet

3RU1116-1GC1 RELAY. Datasheet pdf. Equivalent


Part 3RU1116-1GC1
Description OVERLOAD RELAY
Feature Product data sheet 3RU1116-1GC1 OVERLOAD RELAY, 4.5...6.3 A, 1NO+1NC, SIZE S00, CLASS 10, CAGE CLAM.
Manufacture Siemens
Datasheet
Download 3RU1116-1GC1 Datasheet


Product data sheet 3RU1116-1GC1 OVERLOAD RELAY, 4.5...6.3 A 3RU1116-1GC1 Datasheet
Recommendation Recommendation Datasheet 3RU1116-1GC1 Datasheet




3RU1116-1GC1
Product data sheet
3RU1116-1GC1
OVERLOAD RELAY, 4.5...6.3 A, 1NO+1NC,
SIZE S00, CLASS 10,
CAGE CLAMP CONNECTION,
FOR INSTALLAT. AS A SINGLE UNIT
General technical data:
product brand name
product designation
Size of overload relay
Number of poles / for main current circuit
Product function / removable terminal for auxiliary and control
circuit
Impulse voltage resistance / rated value
Protection class IP / on the front
Protection against electrical shock
Installation altitude / at a height over sea level / maximum
Resistance against shock
Ambient temperature
• during transport
• during storage
• during operating
Relative humidity / during operating phase / maximum
type of protection
Active power loss / total / typical
Size of the contactor / can be combined / company-specific
SIRIUS
thermal overload relay
S00
3
No
kV 6
IP20
finger-safe
m 2,000
8g / 10 ms
°C -55 … +80
°C -55 … +80
°C -20 … +70
% 100
DMT 98 ATEX G 001
W 6.6
S00
3RU1116-1GC1
Page 1/4
02/12/2013
subject to modifications
© Copyright Siemens AG 2013



3RU1116-1GC1
Main circuit:
Operating current / of the fuse link / rated value
Service power / at AC-3
• at 400 V
Type of assignement
Auxiliary circuit:
Number of NC contacts / for auxiliary contacts
Number of NO contacts / for auxiliary contacts
Number of change-over switches / for auxiliary contacts
Design of the fuse link / for short-circuit protection of the
auxiliary switch / required
Operating current / of the auxiliary contacts / at AC-15
• at 24 V
• at 110 V
• at 120 V
• at 125 V
• at 230 V
• at 400 V
Operating current / of the auxiliary contacts / at DC-13
• at 24 V
• at 110 V
• at 125 V
• at 220 V
Protection function:
Trip class
Adjustable response current
• of the current-dependent overload release
Installation/mounting/dimensions:
Type of mounting
mounting position
Depth
Height
Width
Connections:
Design of the electrical connection
• for main current circuit
A 20
kW 2.2
2
1
1
0
fuse gL/gG: 6 A, quick: 10 A
A3
A3
A3
A3
A2
A1
A1
A 0.22
A 0.22
A 0.11
CLASS 10
A 4.5 … 6.3
stand-alone installation
with vertical mounting surface +/-135° rotatable, with
vertical mounting surface +/- 45° tiltable to the front
and back
mm 78
mm 92
mm 45
Cage Clamp terminals
3RU1116-1GC1
Page 2/4
02/12/2013
subject to modifications
© Copyright Siemens AG 2013







@ 2014 :: Datasheetspdf.com :: Semiconductors datasheet search & download site (Privacy Policy & Contact)