Document
Industrial Power Supplies
TSP-Series
Innovative and Powerful Features! ◆ Rugged metal case for
harsh industrial environments
◆ Shock and vibration proof ◆ Worlwide Safety approval package. ◆ ATEX certification tested in accordance
to IECEX (opt. EX)
◆ Model TSP 090-124N meets NEC class 2 ◆ Industrial operating temperature range:
–25°C to +70°C
◆ Adjustable output voltage ◆ Protection against short-circuit,
overvoltage and over-temperature
◆ Power OK signal, Remote On/Off ◆ Wall mounting (opt.) ◆ 3-year product warranty
CB
Scheme
EMC
IEC 60950-1
LVD
UL 60950-1 UL 508
UL 60079-15
ATEX II3G
The TSP series comprises high performance DIN-rail mount power supplies designed for reliable operation under difficult factory floor conditions. High immunity against electrical disturbances and rugged metal casing make these modules the best choice to power sensitive loads in industrial process control systems, machine tools or other demanding industrial applications. They provide a DC-OK signal and external shut down function. Detachable screw terminal blocks make the connection easy.
Function Modules (see page 5)
This power supply line is accompanied by a wide range of function modules for reliable system solutions:
Redundancy modules for true current sharing in parallel operation and for redundant systems. Battery controller modules to configure high reliable UPS systems for 12, 24 and 48 VDC. Selection of battery packs available. Buffer modules for protection against short time AC power loss. Maintenance free! No batteries required.
Models
Order Code
Output Power (Pmax)
**Output Voltage (Vnom)
TSP 070–112*
72 W
12 VDC
TSP 090–124*
90 W
24 VDC
TSP 090–124N
90 W
24 VDC
TSP 090–148*
96 W
48 VDC
TSP 140–112*
144 W
12 VDC
TSP 180–124*
180 W
24 VDC
TSP 180–148*
192 W
48 VDC
TSP 360–124* TSP 360–148*
360 W
24 VDC 48 VDC
TSP 600–124*
24 VDC
TSP 600–136 600 W
36 VDC
TSP 600–148*
48 VDC
* For ATEX compliant models add appendix -EX to order code.
** Output voltage adjustable 12–14 VDC, 24–28 VDC and 48–56VDC *** Max. current at nominal output voltage and operating temperature up to +40°C max.
http://www.tracopower.com
***Output Current (Imax)
6.0 A 3.75 A 3.75 A 2.0 A 12.0 A 7.5 A 4.0 A 15.0 A 7.5 A 25.0 A 16.5 A 12.5 A
Page 1 of 9
Industrial Power Supplies
TSP Series
70–600 Watt
Input Specifications
Input voltage range
TSP 070/090 85 – 264 VAC universal input
other models: 85 – 132 / 187 – 264 VAC autoselect
output current derating at operation below 100 VAC see graph B, page 4
Input voltage frequency 47 – 63 Hz
Harmonic limits EN 61000-3-2, Class A (for limited output power)
Holdup time
230 VAC 20 ms 115 VAC 10 ms at full load, 20 ms at 66% load
Inrush current 115 VAC
TSP 070/090 < 12 A
TSP 140/180 < 13 A
TSP 360 < 16 A
TSP 600 < 25 A
230 VAC < 20 A < 25 A < 25 A < 30 A
Recommended circuit breaker,
TSP 070/090/140/180 6.0 – 16.0 A
characteristic B
TSP 360 10.0 – 16.0 A
TSP 600 16.0 – 25.0 A
Efficiency 87 % typ.
Output Specifications
Output voltage adj. range
12 VDC models: 12 – 14 VDC
24 VDC models: 24 – 28 VDC
36 VDC model: 36 – 42 VDC
48 VDC models: 48 – 56 VDC
At output voltage higher than nominal output voltage
max. output current has to be reduced accordingly, in
order not to exceed max. output power.
Regulation
– Input variation 0.5 % max. – Load variation (10–100 %) 0.5 % max.
Ripple and Noise (20MHz bandwidth) 100 mV pk-pk typ. (200 mV pk-pk max. at Imax)
Electronic short circuit protection current limitation at Imax. constant current, automatic recovery
Output overvoltage protection
12 VDC models: 20 V
24 VDC models: 35 V
36 VDC model: 43 V
48 VDC models: 60 V
Overload protection electronic overload protection
Overtemperature protection switch off at overtemperature, automatic restart
Power back immunity
12 VDC models: 16 V
24 VDC models: 35 V
36 VDC model: 48 V
48 VDC models: 63 V
Status indicator dual color LED (green: DC ok, red: DC off)
Power OK signal
– trigger threshold:
12 VDC models: 9 – 11 V
24 VDC models: 18 – 22 V
36 VDC model: 27 – 34 V
48 VDC models: 36 – 46 V
– active output signal:
12 VDC models: 11.0 V ±1.0 V
(reference to –Vout) (20 mA max. for TSP 070, 40 mA max. for TSP 140)
24 VDC models: 22.0 V ±2.0V / 20 mA max.
(10 mA max. for TSP 090, 20mA max. for others)
36 VDC model: 34.0 V ±2.0 V / 20 mA max.
48 VDC models: 44.0 V ±4.0 V / 15 mA max.
– relay output DC OK = contact closed
rated: 30 VDC/1.0 A for 12/24 VDC models
rated: 30 VDC/2.0 A for 36 VDC model
rated: 48 VDC/0.5 A .