Current Transducers CT 100-S
Current Transducer CT 100-S
For very accurate measurements of currents : DC, AC, pulsed..., with a galvanic isolation be...
Description
Current Transducer CT 100-S
For very accurate measurements of currents : DC, AC, pulsed..., with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN
=
100 A
Provisional
Electrical data
IP N IP VO U T KN RL CL tC VC IC Vd Primary nominal r.m.s. current Primary current, measuring range Analog output voltage Conversion ratio Load resistance Capacitance loading Output short-circuit duration 1) Supply voltage (± 5 %) Current consumption R.m.s. voltage for AC isolation test, 50 Hz, 1 mn 100 0 .. ± 150 5 100 A / 5 V > 500 ≤5 A A V Ω nF s V mA kV
Features
Closed loop (compensated) current
transducer
Insulated plastic case recognized
according to UL 94-V0
∞
Patent pending.
± 15 90 + VOUT / R L 6
Advanced features
f = 250 kHz X G = ± 0.15 % (- 25°C .. + 70°C).
Accuracy - Dynamic performance data
XG VO tr di/dt f Overall accuracy @ IPN Offset voltage @ IP = 0 - 25°C .. + 70°C TA = 25°C - 25°C .. + 70°C ± 0.15 Typ Max ± 0.4 ± 0.6 % mV mV ns A/µs kHz
Advantages
Excellent accuracy Very good linearity Low temperature drift Optimized response time Wide frequency bandwidth No insertion losses High immunity to external interference Current overload capability.
Response time 2) @ 90 % de IPN di/dt accurately followed Frequency bandwidth (- 3 dB) @ 10 % of IPN
400 60 DC .. 250
General data
TA TS m Ambient operating temperature Ambient storage temperature Mass Standards - 25 .. + 70 °C - 40 .. +...
Similar Datasheet