AC Current transducer AP-B10
AC Current transducer AP-B10
Split core transducer for the electronic measurement AC waveforms current, with galvanic is...
Description
AC Current transducer AP-B10
Split core transducer for the electronic measurement AC waveforms current, with galvanic isolation between the primary (High power) and the secondary circuits (Electronic circuit). Switch selectable ranges and RMS 0-5V and 0-10V switch selectable voltage output.
IPN = 10 .. 400 A
Preliminary
Electrical data
Primary Nominal Current IPN (A.t.RMS) 10,25,50 50,75,100 100,150,200 200,300,400 RL VC Vd Analogue Output Signal VOUT (V) 0-5V or 0-10V 0-5V or 0-10V 0-5V or 0-10V 0-5V or 0-10V Type
Features
RMS output Split core type 5V & 10V switch selectable voltage output. DIN mounting & Panel mounting Eliminates insertion loss Switch selectable ranges
AP 50 B10 AP 100 B10 AP 200 B10 AP 400 B10 ≥ 10 kΩ +24 ±5% V DC 5 kV 18 V
Load resistance Supply voltage R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn Limitation voltage output
Advantages
Large aperture for cable up to Ø18mm High isolation between primary and secondary circuits
Accuracy-Dynamic performance data
Easy to mount < ±1 % of IPN < ±0.5 % of IPN < ±0.5 % of IPN ±1 mV/K ±0.1 %/K < 500 ms 10 .. 6000 Hz
ε
X
L
VOE VOT TC ε G tr f
Accuracy @ IPN, TA = 25°C (without offset) Linearity (0 .. ± IPN) Electrical offset voltage, TA = 25°C Thermal drift of VOE Thermal drift of the gain (% of reading) Response time @ 90% of IP Frequency bandwidth (-3 dB)
Applications
Automation systems Analog current reading for remote monitoring (e.g. motor) and software alarms. Panelmet...