RH 100~1000-P. RH200-P Datasheet


RH200-P 100~1000-P. Datasheet pdf. Equivalent


RH200-P


Coreless Coil Current Transducer RH 100~1000-P
Coreless Coil Current Transducer RH 100 .. 1000-P
For the electronic measurement of currents: AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).

IPN = 100 .. 1000 A

Electrical data
Primary nominal r.m.s. current Type

Features
• • • •
V V kV mA MΩ KΩ No magnetic core Rogowski Coil principle Highly accurate integration circuit Voltage output

IPN (A)
100 200 500 1000 RH 100-P RH 200-P RH 500-P RH 1000-P

VOUT VC Vd IC RIS RL

Output voltage(r.m.s)@ ± IPN, RL = 10 kΩ, TA = 25°C Supply voltage (± 5 %) R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn Current consumption Isolation resistance@ 500 V DC Load resistance

4 ±15 > 2.5 10 > 500 ≥ 100

Advantages
• • • • • •
Wide sensing range Wide frequency range Quick response No hysteresis error No insertion impedance Small size and lightweight

Accuracy-Dynamic performance data

ε

L

VOE VOT TCε G tr f

Linearity (0 .. ± IPN) Electrical offset voltage, TA = 25°C Thermal drift of VOE Thermal drift of the gain (% of reading) Response time @ 90% of IP Frequency bandwidth (±3 dB)

≤ ±0.5 % of IPN ±5 mV ≤ ±0.3 mV/K ±0.03 %/K 1 µs 20Hz .. 100KHz

Applications
• Observing complicated current
waveforms

• High speed and high current • • • • • •
sensing such as IGBT Welding Power unit Electric power regulator Discharge tube Antenna Monitoring for irruptive ...



RH200-P
Coreless Coil Current Transducer
RH 100 .. 1000-P
For the electronic measurement of currents: AC, pulsed, mixed, with
a galvanic isolation between the primary circuit (high power) and the
secondary circuit (electronic circuit).
IPN = 100 .. 1000 A
Electrical data
Primary nominal
r.m.s. current
IPN (A)
100
200
500
1000
Type
RH 100-P
RH 200-P
RH 500-P
RH 1000-P
VOUT
VC
Vd
IC
RIS
RL
Output voltage(r.m.s)@ ± IPN, RL = 10 k, TA = 25°C 4
Supply voltage (± 5 %)
±15
R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn > 2.5
Current consumption
10
Isolation resistance@ 500 V DC
> 500
Load resistance
100
V
V
kV
mA
M
K
Accuracy-Dynamic performance data
εL
V
OE
εVOT
TC
G
tr
f
Linearity (0 .. ± IPN)
Electrical offset voltage, T = 25°C
A
Thermal drift of VOE
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (±3 dB)
±0.5 % of IPN
±5 mV
±0.3 mV/K
±0.03 %/K
1 µs
20Hz .. 100KHz
General data
T Ambient operating temperature
A
TS Ambient storage temperature
m Mass
Min. internal creepage distance/clearance
-10 .. +75 °C
-15 .. +80 °C
20 g
ø11±0.5 m m
Features
No magnetic core
Rogowski Coil principle
Highly accurate integration circuit
Voltage output
Advantages
Wide sensing range
Wide frequency range
Quick response
No hysteresis error
No insertion impedance
Small size and lightweight
Applications
Observing complicated current
waveforms
High speed and high current
sensing such as IGBT
Welding
Power unit
Electric power regulator
Discharge tube
Antenna
Monitoring for irruptive current
Notes :
LEM Components
040714/1
www.lem.com

RH200-P
RH 100 .. 1000-P (in mm)
Specifications subject to change without notice.




@ 2014 :: Datasheetspdf.com :: Semiconductors datasheet search & download site (Privacy Policy & Contact)