AC Current transducer APR-B10
AC Current transducer APR-B10
Split core transducer for the electronic measurement distorted AC waveforms current, with ...
Description
AC Current transducer APR-B10
Split core transducer for the electronic measurement distorted AC waveforms current, with galvanic isolation between the primary (High power) and the secondary circuits (Electronic circuit). Switch selectable ranges and True RMS 0-5V and 0-10V switch selectable voltage output.
IPN = 10 .. 400 A
Preliminary
Electrical data
Primary Nominal Current IPN (A.t.RMS) 10,25,50 50,75,100 100,150,200 200,300,400 RL VC Vd Analogue Output Signal VOUT (V) 0-5V or 0-10V 0-5V or 0-10V 0-5V or 0-10V 0-5V or 0-10V Type
Features
VFD and SCR waveforms current measurement True RMS output Split core type 5V & 10V switch selectable voltage output. DIN mounting & Panel mounting Eliminates insertion loss Switch selectable ranges
APR 50 B10 APR 100 B10 APR 200 B10 APR 400 B10 ≥ 10 kΩ +24 ±5% V DC 5 kV 18 V
Load resistance Supply voltage R.m.s. voltage for AC isolation test, 50/60Hz, 1 mn Limitation of voltage output
Advantages
Large aperture for cable up to Ø18mm
Accuracy-Dynamic performance data
High isolation between primary and secondary circuits < ±1 % of IPN < ±0.5 % of IPN < ±0.5 % of IPN ±1 mV/K ±0.1 %/K < 1000 ms 10 .. 6000 Hz Easy to mount
ε
X
L
VOE VOT TC ε G tr f
Accuracy @ IPN, TA = 25°C (without offset) Linearity (0 .. ± IPN) Electrical offset voltage, TA = 25°C Thermal drift of VOE Thermal drift of the gain (% of reading) Response time @ 90% of IP Frequency bandwidth (-3 dB)
Applications
VFD Controlled Loads: VFD output in...