Document
Terminator I/O Specifications
AC OUTPUT MODULES
T1K-08TA T1K-16TA <---> <--->
Specifications
Outputs per Module Commons per Module Operating Voltage Range Output Voltage Range Max. Load Current ON Voltage Drop Max. Leakage Current Max. Inrush Current Min. Load OFF to ON Response ON to OFF Response Base Power Required Status Indicators Error Status Indications(LEDs ) Fuses (User Replaceable) T1K-FUSE-1 Weight
8 2 (4 pts. / common) isolated 17-240 VAC (47-63Hz) min./max. 15-264 VAC (47-63Hz) min./max. 1A / pt., 4A / common (subject to derating) 1.5VAC @ > 50mA, 4.0VAC @ < 50mA 4mA @ 264 VAC 10A for 10ms 10mA < 1ms < 1ms + 1/2 cycle 250mA @ 5VDC Logic side FU1 ON = fuse 1 blown FU2 ON = fuse 2 blown 2, (10A, 250V / common) 5 x 20 mm type 140g FU1/FU2 ON = fuse 1 or 2 blown FU3/FU4 ON = fuse 3 or 4 blown 4, (10A, 250V / common) 5 x 20 mm type 190g 450mA @ 5VDC
T1K-08TA
16
T1K-16TA
F IELD I/O
8-point and 16-point, AC output modules
The 8-point AC module uses a T1K-08B or T1K-08B-1 base, which is purchased separately. The 16-point AC module uses a T1K-16B or T1K-16B-1 base, which is purchased separately.
4 (4 pts. / common) isolated
Equivalent Output Circuit
w
w
w
.D
at aS
he
et 4U .c
w w w. a u to m at i o n d i re c t . c o m / f i e l d I O
om
Universal Field I/O
7–41
www.DataSheet4U.com
Terminator I/O Dimensions and Installation
DIMENSIONS AND INSTALLATION
It is important to understand the installation requirements for your Terminator I/O system. This will help ensure that the Terminator I/O products work within their environmental and electrical limits.
See the Enclosures section of this desk reference for an enclosure that may be suitable for your application
Plan for safety
This catalog should never be used as a replacement for the technical data sheet that comes with the products or the T1K-INST-M Installation and I/O Manual (It is also available online at www.automationdirect.com.) The technical data sheet contains information that must be followed. The system installation should comply with all appropriate electrical codes and standards.
Unit dimensions and mounting orientation
Use the following diagrams to make sure the Terminator I/O system can be installed in your application. Terminator I/O units can be mounted horizontally or vertically. However, to insure proper airflow for cooling purposes, units should not be mounted upside-down. It is important to check the Terminator I/O dimensions against the conditions required for your application. For example, it is recommended to leave 2” depth for ease of access and cable clearance. However, your distance may be greater or less. Also, check the installation guidelines for the recommended cabinet clearances.
Terminator I/O Environmental Specifications
Ambient Operating Temperature Storage Temperature Ambient Humidity Atmosphere Vibration Resistance Shock Resistance Voltage Withstand (Dielectric) Insulation Resistance Noise Immunity Agency Approvals
32°F to 131°F (0°C to 55°C) -4°F to 158°F (-20°C to 70°C) 5% to 95% (Non-condensing) No corrosive gases. The level of environmental pollution = 2 (UL 840) MIL STD 810C, Method 514.2 MIL STD 810C, Method 516.2 1500VAC, 1 minute 500VDC, 10M ⏲ NEMA ICS3-304 Impulse noise 1µs, 1000V FCC class A RFI (144MHz, 430MHz 10W, 10cm) UL, CE, FCC class A, NEC Class 1 Division 2
48mm (1.89in)
48mm (1.89in)
48mm (1.89in)
89mm (3.5in)
83.3mm (3.28in)
80mm (3.15in)
80mm (3.15in)
80mm (3.15in)
80mm (3.15in)
Power Supply
Network Interface Module
Half-size I/O Module with Base
Full-size I/O Module with Base
System Depth
7–14
Universal Field I/O
1 - 80 0 - 633 - 0405
Terminator I/O Installation
I/O MODULE
I/O module installation
Terminator I/O modules feature separate terminal bases for easy installation. To install I/O modules:
1. Slide the module into its terminal base (until it clicks into position) 2. Hook upper DIN-rail tabs over the top of DINrail, and press the assembly firmly onto the DIN-rail. 3. Slide the module along the DIN-rail until it engages with the adjacent module.
1
DN-ASB angled mounting bracket
Great for mounting in upper locations
F IELD I/O
Great for mounting in lower locations
2 3
Optional angled support bracket raises and tilts the mounting rail for easier access and wiring. Use with 35mm DIN rail. See the Connection Systems in this catalog for details.
Removing I/O modules is a snap
Grip the locking handle, as shown, and pull gently to eject the I/O module from its base. The module will slide out for easy replacement. This procedure does not apply to network interface modules or power supplies, which have integral bases.
Hot swappable I/O modules
You can remove I/O modules under power, but exercise caution while doing so. Do not touch the terminals with your hands or any conductive material. Always remove power when possible.
w w w. a u to m at i o n d i re c t . c o m / f i e l d I O
Universal Field I/O
7–15
Terminator I/O Specifications
POWER SUPPLIES .