Current transducer. AHR-B5 Datasheet

AHR-B5 transducer. Datasheet pdf. Equivalent

AHR-B5 Datasheet
Recommendation AHR-B5 Datasheet
Part AHR-B5
Description AC/DC Current transducer
Feature AHR-B5; AC/DC Current transducer AHR-B5 The transducer for the electronic measurement of DC & distorted AC w.
Manufacture LEM
Datasheet
Download AHR-B5 Datasheet





LEM AHR-B5
AC/DC Current transducer AHR-B5
The transducer for the electronic measurement of DC & distorted AC
waveform currents, with galvanic isolation between the primary circuit
(power) and the secondary circuit (measurement).
True RMS 0-5 V voltage output.
IPN = 500 .. 2000 A
Electrical data
Primary nominal
DC & AC current
IPN (At rms)
500
800
1000
1500
2000
Primary AC current
max. peak value 1)
IP (A)
2000
2500
2000
2500
3000
Output voltage
(Analog)
VOUT (VDC)
0-5
0-5
0-5
0-5
0-5
R L Load resistance
VC Supply voltage
I Current Consumption
C
VSL Output voltage limitation
Î Overload capability (Ampere Turns)
P
Performance data
X
εL
VOE
TCV
OE
TCV
OUT
tr
BW
Accuracy @ IPN, TA = 25°C (excluding offset)
Linearity error (1% of IPN .. ± IPN)
Electrical offset voltage, TA = 25°C
Temperature coefficient of V (0 .. + 60 °C)
OE
(- 40 .. + 70 °C)
Temperature coefficient of V (% of reading)
OUT
Response time to 90% of IPN step
Frequency bandwidth (±1 dB)
General data
TA
T
S
m
IPxx
Ambient operating temperature
Ambient storage temperature
Mass
Protection degree
Type
AHR 500 B5
AHR 800 B5
AHR 1000 B5
AHR 1500 B5
AHR 2000 B5
10
k
+ 20 .. 50 V DC
35 mA
<7 V
30000
At
< ± 1 % of IPN
< ± 1.0 % of IPN
< ± 1.0 % of IPN
± 2.0 mV/K
± 4.0 mV/K
± 0.15 %/K
< 150
ms
DC, 20 .. 6000Hz
- 40 .. + 70
- 40 .. + 85
650
IP20
°C
°C
g
Features
DC + distorted AC waveform currents
measurement
True RMS output
Busbar or panel mounting
Split core type
Insulated plastic case recognized
according to UL94-V0.
Advantages
High isolation between primary and
secondary circuits
Eliminates insertion loss
Easy installation.
Applications
AC power supplies or Motors:
True RMS current sensing - the most
accurate way to monitor power supply
or motor input power
VFD Controlled Loads:
VFD output current monitoring to
indicate how the motor and the
attached load are operating
SCRs or Switch-mode Rectifiers:
Accurate measurement of output
current
Note :
1) The max. peak AC current is the highest peak level of the primary signal that is
taken into account for accurate True r.m.s. calculation.
Yet the device is designed for maximum continuous true r.m.s. value equal to IPN,
whereas the output is limited by the above specified output limitation.
Renewable Energy Installations or
Backup Batteries:
Continuous condition minitoring
allowing automatic failure detection/
anticipation.
Application domain
061128/6
Energy and Automation
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/3
www.lem.com



LEM AHR-B5
Current Transducer AHR-B5
Isolation characteristics
Vb Rated isolation voltage rms 1)
500 V
with IEC 61010-1 according to the 61326 standards and following conditions:
- Reinforced isolation
- Over voltage category III
- Pollution degree PD2
- Heterogeneous field
Vd Rms voltage for AC isolation test 2) , 50 Hz, 1min
dCp Creepage distance
5.8
11.9
kV
mm
dCl Clearance distance
11.9
mm
CTI Comparative tracking index (Group I)
250-399
Notes : 1) If insulated cable is used for the primary circuit, the voltage category could
be improved according to the insulation characteristics given by the cable
manufacturer.
2) Between primary (completely filling the aperture) and secondary.
Output polarity with DC input
Output in V
5
-Ipn 0 +Ipn
Safety
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the
manufacturer’s operating instructions.
Installation and maintenance should be done with main power supply
disconnected.
The operator must have an accreditation to install this material.
Caution! Risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (e.g. primary conductor, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
The user must take care of all protection guarantee against electrical shock.
This transducer is a built-in device, whose conducting parts must be inaccessible
after installation. A protective housing or additional shield could be used.
061128/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 2/3
www.lem.com



LEM AHR-B5
Dimensions AHR-B5 (in mm. 1 mm = 0.0394 inch)
17 4
10 4
22. 28
35 5.5 0
25 20
9 . 10
5 0.50
54 . 10
20 .34
15
55
1 10
15 0
Connections
Wires up to 2 mm
Female connector provided (screw terminals)
Output Connector
1(Vcc) 2(NC) 3(Vout) 4(GND)
AHR
24 VDC Power
(+)
(-)
(-) (+)
Load
(Controller, meter etc)
+24VDC
Is
OUT
Ip
GND
Mechanical characteristics
General tolerance
Primary aperture
Busbar fastening
Panel mounting
Distance between hole axes
± 1 mm
104 x 40 mm
1 hole 5.5 mm &
2 slots 5.5 x 30 mm
4 holes 3.2 mm
15 x 150 mm
Remarks
The return busbar and primary conductor elbow must be
located at a minimum distance of 2.5 x the window length
away from the transducer case.
The temperature of the primary busbar can not exceed
90°C.
Dynamic performances are the best with a primary busbar
completely filling the primary aperture.
This is a standard model. For different versions (supply
voltages, different outputs, bidirectional measurements...),
please contact us.
061128/6
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 3/3
www.lem.com