4-Line Filters. B84299-K36 Datasheet


B84299-K36 Filters. Datasheet pdf. Equivalent


B84299-K36


(B84299-K3x) 4-Line Filters
4-Line Filters for Installations and Systems
Power line filters for three-phase systems with additional VHF suppression Rated voltage 440/250 V~, 50/60 Hz Rated current 6 to 75 A Construction
s Four-line filter s Metal case s Screw-type cable fitting for strain relief

B84299-K33 … B84299-K39

on line side, edge protector on load side
s Feed-through capacitors

Features
q High insertion loss up to the GHz range

Applications
q Power supplies for industrial installations q Medical engineering s Packaging machines
www.DataSheet4U.com Terminals

s Safe-to-touch terminal clamps incorporated in case

Marking Marking on component: Manufacturer’s logo, ordering code, rated voltage, rated current, date code Minimum marking on packaging: Manufacturer’s logo, ordering code

304 03/01

4-Line Filters for Installations and Systems
Circuit diagram

B84299-K33 … B84299-K39

L1

L1’

L2
LINE Netz

L2’
LOAD Last

L3

L3’

N

N’

SSB0543-U

Typical circuit taking the example of B84299-K35

Technical data Rated voltage V R Rated current IR Test voltage VP Leakage current l leak Climatic category 440/250 V~, 50/60 Hz referred to 40 °C ambient temperature 1414 V–, 2 s (line/line) 2700 V–, 2 s (lines/case) at 400 V~, 50 Hz in accordance with EN 60068-1 40/085/21 (– 40 °C/+ 85 °C/21 days damp heat test)

Characteristics and ordering codes IR A 6 16 25 50 75 l leak mA < 5 < 5 < 5 < 5 < 10 Terminal cr...



B84299-K36
4-Line Filters
for Installations and Systems
Power line filters for three-phase systems
with additional VHF suppression
Rated voltage 440/250 V~, 50/60 Hz
Rated current 6 to 75 A
Construction
s Four-line filter
s Metal case
s Screw-type cable fitting for strain relief
on line side, edge protector on load side
s Feed-through capacitors
Features
q High insertion loss up to the GHz range
Applications
q Power supplies for industrial installations
q Medical engineering
s Packaging machines
www.DataSheet4TUe.cromminals
s Safe-to-touch terminal clamps incorporated in case
Marking
Marking on component:
Manufacturers logo, ordering code,
rated voltage, rated current, date code
Minimum marking on packaging:
Manufacturers logo, ordering code
B84299-K33
… B84299-K39
304 03/01

B84299-K36
4-Line Filters
for Installations and Systems
Circuit diagram
B84299-K33
… B84299-K39
L1
L2
LNINetEz
L3
N
L1
L2
LLaOstAD
L3
N
Typical circuit taking the example of B84299-K35
SSB0543-U
Technical data
Rated voltage VR
Rated current IR
Test voltage VP
Leakage current l leak
Climatic category
440/250 V~, 50/60 Hz
referred to 40 °C ambient temperature
1414 V, 2 s (line/line)
2700 V, 2 s (lines/case)
at 400 V~, 50 Hz
in accordance with EN 60068-1
40/085/21 (40 °C/+ 85 °C/21 days damp heat test)
Characteristics and ordering codes
IR
l leak
Terminal
Approx.
cross section weight
A
mA mm2
kg
6
<5
4
16
<5
4
25
<5
4
50
<5
16
75
< 10
25
1,8
2,1
3
7,5
11
Ordering code
B84299-K33
B84299-K35
B84299-K36
B84299-K37
B84299-K39
Approvals
×
× (for 14 A)
× (for 20 A)
× (for 40 A)
× (for 65 A)
305 03/01