BLP30; www.DataSheet4U.com BLP30 AC-DC Series Data Sheet 30 Watts Features • • • • • • • • • • • RoHS compliant for all six substances 2 ” x 4” footprint Component height l ess than 1” 25 W rating with natural convection cooling 30 W rating with 10 CFM airflow Compliance to EMI Class B U niversal AC input Short-circuit protect ion Overvoltage protection CE marked to Low Volt.


Power-One BLP30

age Directive (Pending) Compliance to EN 61000-4-2/-3/-4/-5/-6/-8/-11 Two-year w arranty Applications • • • • • • Datacom (hubs, routers) POS terminals Industrial Cable modems Exter nal disk storage Medical instrumentatio n Computers Description The BLP30 Seri es’ economical and compact constructi on provides single or three-output AC t o DC power conversion to meet the .


Power-One BLP30

requirements of most commercial and indu strial applications. Single-Output Mod el Selection Model Nominal Output Volta ge (VDC) 5V 12V 24V Min-Max Output Cur rent (Amps), Convection 0–5 0 – 2.1 0 – 1.0 Min-Max Output Current (Amp s), 1 Forced Air 0–6 0 – 2.5 0 – 1.25 Peak Output Current (Amps) 2 7.2 3.0 1.5 Total Regulation 3 (%) ±2 ±2 ±2 Ripple & Noise 4 pk-pk % 1 .



Part

BLP30

Description

Changing the Shape of Power

Manufacture

Power-One

Datasheet
Download BLP30 Datasheet




 BLP30
www.DataSheet4U.com
BLP30 AC-DC Series Data Sheet
30 Watts
Applications
Datacom (hubs, routers)
POS terminals
Industrial
Cable modems
External disk storage
Medical instrumentation
Computers
Features
RoHS compliant for all six substances
2” x 4” footprint
Component height less than 1”
25 W rating with natural convection cooling
30 W rating with 10 CFM airflow
Compliance to EMI Class B
Universal AC input
Short-circuit protection
Overvoltage protection
CE marked to Low Voltage Directive (Pending)
Compliance to EN61000-4-2/-3/-4/-5/-6/-8/-11
Two-year warranty
Description
The BLP30 Series’ economical and compact construction provides single or three-output AC to DC power
conversion to meet the requirements of most commercial and industrial applications.
Single-Output Model Selection
Model
BLP30-1005G
Nominal
Output Voltage
(VDC)
5V
BLP30-1012G
12V
BLP30-1024G
24V
Min-Max Output
Current (Amps),
Convection
0–5
0 – 2.1
0 – 1.0
Min-Max Output
Current (Amps),
Forced Air 1
0–6
0 – 2.5
0 – 1.25
Peak Output
Current
(Amps) 2
7.2
3.0
1.5
Total
Regulation
(%) 3
±2
±2
±2
Ripple &
Noise
pk-pk % 4
1
1
0.6
Triple-Output Model Selection
Model
BLP30-3000G
Nominal
Output Voltage
(VDC)
+5V
+12V
-12V
Min-Max Output
Current (Amps),
Convection
0.2 – 2.5
0.1 – 1.2
0.0 – 0.3
Min-Max Output
Current (Amps),
Forced Air 1
0.2 – 3.5
0.1 – 2.0
0.0 – 0.5
Peak Output
Current
(Amps) 2
5
3
1
Total
Regulation
(%) 3
±2
±5
±5
Ripple &
Noise
pk-pk % 4
1%
1%
1%
1 10 CFM or 260 LFM (average measurement of six equally-distributed points through a 3.5" x 1.6" (9 cm x 4 cm) cross-sectional area with
power supply mounted on a 0.25" (6.35 mm) standoffs. Recommended airflow direction is from the AC input to the DC output.
2 Peak current duration for less than 30 seconds with a max duty cycle of 10%.
3 At 25 °C ambient including voltage set point tolerance, line, and load regulation
4 Maximum peak-to-peak noise expressed as a percentage of output voltage, 20 MHz bandwidth, measured with a twisted pair differentially
across a 10 µF E-cap and a 0.1 µF ceramic cap in parallel. The point of measurement is within 1 cm of the output connection.
JUL 05, 2006 revised to DEC 05, 2006
Page 1 of 6
www.power-one.com





 BLP30
BLP30 AC-DC Series Data Sheet
30 Watts
ELECTRICAL SPECIFICATIONS
Input Specifications
Parameter
Input Voltage - AC
Input Voltage - DC
Input Frequency
Input Current
Inrush Surge Current
Conditions/Description
Single-phase continuous input range
AC Input
At 90 VAC input., 30W
Internally limited. 115 VAC, Max Power, 25 °C
Internally limited. 230 VAC, Max Power, 25 °C
Input fuse
Efficiency
Switching Frequency
Non-user serviceable internally located AC
input line fuse is provided.
At maximum output power.
Min.
90
127
47
Nom.
100 - 250
160/325
50 - 60
0.75
Max.
264
375
63
16
32
70 75
60 69
Output Specifications
Parameter
Output power
Conditions/Description
With convection cooling. See Model Selection.
With forced-air cooling. See Model Selection.
Load transient
Vo1, Vo2, or Vo3 deviation due to a 50 to 100%
load change at a rate of 1A/µs.
Turn on Delay
Time required for outputs to be within regulation
after initial application of AC input.
Rise Time
Time required for output voltage to rise from
10% to 90%.
Hold-up Time
At 30W, 115 VAC, 60 Hz.
Overvoltage Protection Main output.
5V:
12V:
24V:
Short-circuit Protection Fully-protected against output short circuit.
Overshoot
Single-output models.
Overshoot
Triple-output models.
Min.
20
5.6
14.0
29.0
Nom.
Max.
25
30
±5
1.5
20
6.9
16.7
34.2
2
5
Units
VAC
VDC
Hz
A rms
A pk
A pk
%
kHz
Units
Watts
%
Sec
ms
Ms
V
%
%
JUL 05, 2006 revised to DEC 05, 2006
Page 2 of 6
www.power-one.com





 BLP30
BLP30 AC-DC Series Data Sheet
30 Watts
Regulatory & Safety Approvals
Parameter
Conditions/Description
UL60950-1
All models are approved.
CSA-C22.2,
No. 60950-1-03
All models are approved.
EN 60950-1
/IEC 60950-1
All models are approved.
CE Mark for LVD
All models are approved.
CB Approval
Completed.
Ground Continuity
At 12 VDC.
Dielectric Withstand
Voltage
Input-to-Ground (Basic)
.
Input-to-Output (Reinforced). The primary to
secondary test is not performed on completed
assemblies.
Output-to-Ground (Functional).
Electromagnetic
Interference
FCC Part 15.
CISPR 22 and CISPR 11.
Conducted:
Conducted:
ESD
Per EN 61000-4-2, level 2.
Radiated Susceptibility Per EN 61000-4-3, level 3.
EFT/Burst
Per EN 61000-4-4, level 3.
Input Transient
Protection
Per EN 61000-4-5, class 3. Line-to-Line:
Line-to-Ground:
RF Immunity
Per EN 61000-4-6, level 3.
Magnetic Fields
Per EN 61000-4-8.
Voltage Interruptions Per EN 61000-4-11
Leakage Current
Per EN 60950
At 115 VAC:
At 230 VAC:
Min.
2121
4242
500
B
B
1
1
2
Nom.
3
3
1
Max.
30
0.2
0.4
Units
A
VDC
VDC
VDC
Class
V/m
kV
kV
V/m
A/m
mA
JUL 05, 2006 revised to DEC 05, 2006