Power Shelves. AFS2400 Datasheet

AFS2400 Shelves. Datasheet pdf. Equivalent

Part AFS2400
Description (AFS2400 / AFS4800) Rack Mountable Power Shelves
Feature AFS2400 and AFS4800 Rack Mountable Power Shelves • • • • • Front-end shelves for AFE1200 series powe.
Manufacture Artesyn Technologies
Datasheet
Download AFS2400 Datasheet



AFS2400
www.DataSheet4U.com
[ 2 YEAR WARRANTY ]
AFS2400 and AFS4800
Rack Mountable Power Shelves
• Front-end shelves for AFE1200 series power supplies
• Distributed power architecture
• UL and TUV approval
• Hot-swap power system
• N+1 redundancy
The AFS2400 and AFS4800 power shelves are designed to house Artesyn standard
AFE1200 series front-end power supplies. The shelves mount into standard 19 inch
racks. The power shelves accept full range (85 to 264VAC) AC power and deliver a
regulated DC bus voltage generated from the AFE1200 power supplies. The power
shelf provides input filtering and protection, and individual 20 Amp circuit breakers for
each AFE1200 power supply are provided on the front end of the shelf. An output bus
bar on the rear of the unit is provided for distribution of the main output to system
payload. Control, diagnostic and protection signals and the auxiliary output from
AFE1200 power supplies are routed through the power shelf to a parallel interface
connector on the rear of the unit. Clearance is provided on the rear of the unit to
maintain adequate airflow and cooling of the AFE1200 power supplies mounted within
the shelf.
POWER SHELF
AFS2400-2U2P
AFS4800-4U4P
MAIN OUTPUT
POWER
2400W
N+1 REDUNDANT
POWER
1200W
HEIGHT
2U (3.5 inch)
AFE1200 POWER
SUPPLIES
2
4800W
3600W
4U (7.0 inch)
AFS Power Shelf Characteristics
4
SIGNAL
INTERFACE
Parallel via 25 pin D
type connector
Parallel via 37 pin D
type connector
POWER SHELF
AFS2400-2U2P
AFS4800-4U4P
POWER MODULE
AFE1200-96S48NA
48V @ 50A
48V @ 100A
AFE1200-96S24NA
24V @ 100A
12V @ 2A
24V @ 200A
12V @ 4A
AFE1200 Output Configurations with AFS Power Shelves
Nominal Input Voltage
85VAC
120VAC
220VAC
240VAC
Line Current (Typical)
17.5A rms
12.1A rms
6.5A rms
6.0A rms
AC Input Line Cord Current
(for each AFE1200 module within power shelf)
PAGE 1



AFS2400
AFS2400/4800 Power Shelves
AFS2400 and AFS4800 Rack-mountable
power shelves for AFE1200 series modules
Mechanical Notes for AFS2400-2U2P Interface Drawing
1 All dimensions in inches (mm).
13.81 (350.77)
www.DataSheet4U.com
17.33
(440.18)
AFS 2400-2U2P
MODLAR POWER SYSTEM
TWO 1200W HOT PLUGGABLE POWER SUPPLIES OPTIONAL SYSTEM
CONTROL MODULE 2U HIGH, 19 INCH SHELF DESIGN
NORMAL
AIR FLOW
CUSTOMER SIGNAL CONNECTOR
25 POSITION DSUB RECEPTACLE
MATE - 25 POS DSUB PLUG
ALLOW 6.0" MIN CLEARANCE
BOTH FRONT AND BACK
FOR ADEQUATE COOLING
DC OUTPUT TERMINALS
#10 STUDS
POS
NEG
CUSTOMER
AC INPUT CONNECTORS
MATE - HUBBELL H320C
REAR VIEW OF SHELF
WITH COVER REMOVED FOR CLARITY
MOUNTING BRACKETS
OPTIONAL LOCATION
1.50
(38.10) REF
0.12
(3.05)
0.265
(6.731)
AC SECTION
BREAKERS / LINE FILTERS
0.500
(12.700)
1200 WATT
HOT PLUGGABLE
POWER SUPPLIES
AC POWER A
A
MODULE
AC POWER B
0.93 (2.362) REF
CLEARANCE TO ACCOMMODATE
CABINET RAIL MTG/SUPPORT
OPEN FULLY-INSERT UNIT
V+
AC
GOOD
FAIL
PWR
GOOD
V-
18.2 (462.3)
18.98 (482.09)
POWER SYSTEM
OPTIONAL CARD SLOT
OPEN FULLY-INSERT UNIT
3.000
V+ (76.200)
AC
GOOD
B
FAIL
MODULE
PWR
3.47GOOD
V-
(88.14)
0.235
(5.969)
ALL MEASUREMENTS INCHES (MM)
International Safety Standard Approvals
AFS4800-4U4P safety approval is pending
EN60950/IEC950 File No. E9972397
UL1950 File No. E135734
Please consult our website for the following items: Application Note
http://www.artesyn.com
PAGE 2







@ 2014 :: Datasheetspdf.com :: Semiconductors datasheet search & download site (Privacy Policy & Contact)