Phase Sequence Relay



Feature


BV1 - Phase sequence relay Application S upervision of phase loss, phase sequenc e and undervoltage in three-phase syste ms. Function Relay BV1 measures amplit ude and angle of three phase voltages. The angle of the phasors determine the phase sequence. Unbalance and phase los s are detected by the measurement of am plitude and angle. www.DataSheet4U.com The undervoltage t.
Manufacture

Woodward

Datasheet
Download BV1 Datasheet


Woodward BV1

BV1; rip setting is 70 % of Un fixed. The und erfrequency element trips if the freque ncy falls below 45 Hz. Technical data rated voltage Un: frequency range: hyst eresis: power consumption: thermal load carrying capacity: returning time: min imum operating time: 110 V, 230 V, 400 V AC 45 - 66 Hz 2% Un 3 VA (4 VA BA1-4 00) continuously 1,3 x Un 700 ms 700 ms Fig. 1: Front pl.


Woodward BV1

ate Output relays: max. breaking capaci ty ohmic: 250 V AC/120 W DC inductive: 500 V AC/75 W DC rated current: 5A maki ng current (16ms): 20 A System data: re gulations: VDE 0435 Teil 303 temperatur e range at storage and operation: - 25 C bis + 70°C Mechanical stress: shock : class 1 acc. to DIN IEC 255-21-2 vibr ation: class 1 acc. to DIN IEC 255-21-1 degree of protectio.


Woodward BV1

n: weight: mounting position: IP 40 at c losed front cover approx. 0,5 kg any T he unit BV1 is designed to be fastened onto a DINrail acc. to DIN EN 50022 sam e as all units of the BASIC LINE. The f ront plate of the unit is protected wit h a sealable transparent cover (IP40). Please remove the transparent cover wit h a screw driver to adjust the relay. LED LED is used to.

Part

BV1

Description

Phase Sequence Relay



Feature


BV1 - Phase sequence relay Application S upervision of phase loss, phase sequenc e and undervoltage in three-phase syste ms. Function Relay BV1 measures amplit ude and angle of three phase voltages. The angle of the phasors determine the phase sequence. Unbalance and phase los s are detected by the measurement of am plitude and angle. www.DataSheet4U.com The undervoltage t.
Manufacture

Woodward

Datasheet
Download BV1 Datasheet




 BV1
BV1 - Phase sequence relay
Application
Supervision of phase loss, phase sequence and
undervoltage in three-phase systems.
Function
Relay BV1 measures amplitude and angle of three
phase voltages. The angle of the phasors determine
the phase sequence. Unbalance and phase loss are
www.DataSheet4U.cdoemtected by the measurement of amplitude and angle.
The undervoltage trip setting is 70 % of Un fixed.
The underfrequency element trips if the frequency falls
below 45 Hz.
Technical data
rated voltage Un:
frequency range:
hysteresis:
power consumption:
thermal load carrying
capacity:
returning time:
minimum operating
time:
110 V, 230 V, 400 V AC
45 - 66 Hz
2% Un
3 VA (4 VA BA1-400)
continuously 1,3 x Un
700 ms
700 ms
Output relays:
max. breaking capacity
ohmic:
250 V AC/120 W DC
inductive:
500 V AC/75 W DC
rated current:
5A
making current (16ms): 20 A
System data:
regulations:
VDE 0435 Teil 303
temperature range at
storage and operation: - 25°C bis + 70°C
Mechanical stress:
shock:
class 1 acc. to DIN IEC 255-21-2
vibration:
class 1 acc. to DIN IEC 255-21-1
degree of protection: IP 40 at closed front cover
weight:
approx. 0,5 kg
mounting position: any
Fig. 1: Front plate
The unit BV1 is designed to be fastened onto a DIN-
rail acc. to DIN EN 50022 same as all units of the
BASIC LINE.
The front plate of the unit is protected with a sealable
transparent cover (IP40).
Please remove the transparent cover with a screw
driver to adjust the relay.
LED
LED is used to indicate operation without fault with
steady light. At tripping or underfrequency the LED
extinguishes.
110
65
Fig. 2: Dimensional drawing of BV1
TB BV1 03.97 E
1




 BV1
Auxiliary voltage supply
The unit BV1 needs no separate auxiliary voltage
supply. The supply voltage can be formed directly from
the measuring quantity.
Unit dead, wrong phase
sequence or tripped
www.DataSheet4U.com
Fig. 3: Connection diagram
Operation without a fault
Fig. 4: Contact positions
Connection terminals
The connection up to a maximum of 2 x 2,5 mm²
cross-section conductors is possible. For this procedure
the transparent cover of the unit has to be removed.
Order key:
quantity
BV1
110 V AC
230 V AC
400 V AC
-
110
230
400
2 TB BV1 03.97 E