DatasheetsPDF.com

Front-End 1U. DS650-5 Datasheet

DatasheetsPDF.com

Front-End 1U. DS650-5 Datasheet






DS650-5 1U. Datasheet pdf. Equivalent




DS650-5 1U. Datasheet pdf. Equivalent





Part

DS650-5

Description

AC-DC / Distributed Power Front-End 1U



Feature


Embedded Power for Business-Critical Con tinuity DS650/DS850 650 / 850 Watts Di stributed Power System Distributed Powe r Bulk Front-End Total Output 650/850 W atts Power: +3.3 Vdc Stand-by Output Wi de Range 90 - 264Vac Input Voltage: 12, 24 and 48V Rev. 05.29.08 DS650 and DS 850 1 of 4 Electrical Specifications S pecial Features • Active power factor correction • EN6100.
Manufacture

Emerson

Datasheet
Download DS650-5 Datasheet


Emerson DS650-5

DS650-5; 0-3-2 harmonic compliance • Active AC inrush control • 1U X 2U form factor • 15.4W/ in3 • 12 Vdc, 24 Vdc and 4 8 Vdc output • +3.3 Vdc stand-by (5V standby - consult factory) • No minim um load required • Hot plug operation • N + 1 redundant • Internal OR'in g fets • Active current sharing (10 - 100% load) • Built-in cooling fans ( 40mm x 28mm) • I2C communication interfa.


Emerson DS650-5

ce bus • EERPOM for FRU data • Red/G reen bi-color LED status • Internal f an speed control • Fan Fail Tach outp ut signal • INTEL, SSI Std. logic tim ing • INTEL, SSI Std. FRU data format • One year warranty Input Input ran ge Frequency Inrush current Efficiency Conducted EMI Radiated EMI Power factor Leakage current Hold up time 90-264 Va c (wide range) 47-63 Hz, single .


Emerson DS650-5

phase AC 55 A maximum inrush current >82 % typical at full load, high line FCC S ubpart J EN55022 Class B FCC Subpart J EN55022 Class B 0.99 typical 1.40 mA @ 240 Vac 20ms minimum +12 V @ 52.5 A/70. 0 A +24 V @ 26.3 A / 35.0 A +48 V @ 13. 1 A / 17.5 A +3.3 vsb @ 6 A (5 V @ 4 A available) Factory Set, no pot adjustme nts Main output; +5%/-5% +3.3 vsb; +5%/ -5% 110% - 150% of.

Part

DS650-5

Description

AC-DC / Distributed Power Front-End 1U



Feature


Embedded Power for Business-Critical Con tinuity DS650/DS850 650 / 850 Watts Di stributed Power System Distributed Powe r Bulk Front-End Total Output 650/850 W atts Power: +3.3 Vdc Stand-by Output Wi de Range 90 - 264Vac Input Voltage: 12, 24 and 48V Rev. 05.29.08 DS650 and DS 850 1 of 4 Electrical Specifications S pecial Features • Active power factor correction • EN6100.
Manufacture

Emerson

Datasheet
Download DS650-5 Datasheet




 DS650-5
Embedded Power for
Business-Critical Continuity
DS650/DS850
650 / 850 Watts
Distributed Power System
Distributed Power Bulk Front-End
Total Output 650/850 Watts
Power:
+3.3 Vdc Stand-by Output
Wide Range 90 - 264Vac
Input Voltage: 12, 24 and 48V
Rev. 05.29.08
DS650 and DS850
1 of 4
Special Features
• Active power factor correction
• EN61000-3-2 harmonic compliance
• Active AC inrush control
• 1U X 2U form factor
• 15.4W/ in3
• 12 Vdc, 24 Vdc and 48 Vdc output
• +3.3 Vdc stand-by
(5V standby - consult factory)
• No minimum load required
• Hot plug operation
• N + 1 redundant
• Internal OR'ing fets
• Active current sharing
(10 - 100% load)
• Built-in cooling fans
(40mm x 28mm)
• I2C communication interface bus
• EERPOM for FRU data
• Red/Green bi-color LED status
• Internal fan speed control
• Fan Fail Tach output signal
• INTEL, SSI Std. logic timing
• INTEL, SSI Std. FRU data format
• One year warranty
Safety
UL/cUL 60950 (UL Recognized)
NEMKO+ CB Report EN60950
EN60950
CE Mark
China CCC
Electrical Specifications
Input
Input range
90-264 Vac (wide range)
Frequency
47-63 Hz, single phase AC
Inrush current
Efficiency
Conducted EMI
55 A maximum inrush current
>82% typical at full load, high line
FCC Subpart J EN55022 Class B
Radiated EMI
Power factor
FCC Subpart J EN55022 Class B
0.99 typical
Leakage current
1.40 mA @ 240 Vac
Hold up time
20ms minimum
Output
Main DC voltage
Stand-By
+12 V @ 52.5 A/70.0 A
+24 V @ 26.3 A / 35.0 A
+48 V @ 13.1 A / 17.5 A
+3.3 vsb @ 6 A (5 V @ 4 A available)
Adjustment range
Factory Set, no pot adjustments
Regulation
Over current
Over voltage
Under voltage
Turn-on delay
Main output rise time
Main output; +5%/-5%
+3.3 vsb; +5%/-5%
110% - 150% of nominal Latches off if overcurrent lasts
over 1 second, otherwise it is auto recovery.
+3.3 vsb, 9 A max (hiccup mode)
110% - 120% of nominal
+3.3 vsb; 3.76 - 4.30 Vdc
75% - 90% of nominal
2 Second max, 5 - 50 mS, Monotonic Rise
5 - 50 mS, Monotonic Rise




 DS650-5
Logic Control
PS_SEATED
PWR GOOD
TTL logic LOW if power supply is seated into system
connector. This is a short pin. A logic HIGH if the PSU is
removed.
Active TTL HiIGH when output is within regulation limits.
AC OK
Temp OK
PS_INHIBIT/PS_KILL
A LOW logic level if the input voltage is within allowable
limits. A TTL logic HIGH level, and a 5mS early warning
signal before main output loss of regulation.
A TTL logic HIGH, when operating within allowable
temperature range.
This signal is connected to a short pin on the PSU
When left open power supply operation will be inhibited.
When the power supply is inserted into the system, this
pin will be pull low by the system and turn the power sup-
ply on only after all other power supply pins have seated.
Environmental Specifications
Operating temperature:
-10° to 50°C ; 50% power derating at 70°C
Storage temperature:
-40°C to +85°C
Altitude, operating 10,000ft.
Electromagnetic
-EN61000-3-2, -3-3
susceptibility / Input transients: -EN61000-4-2, 4.3, 4-4, -4-5, 4-11 Level
-EN55024:1998
RoHS & lead-free compliant (no tantalum caps.)
Humidity:
20 to 90% RH, non-condensing
Shock and vibration specificatons complies with Astec Std. Specifications, Q3205
MTBF (Demonstrated)
500K Hrs at full load, 40°C
Ordering Information
Output
DS650-3
Nominal Output
Voltage Set Point
12.0 Vdc
3.3 vsb*
DS650-5
DS650-9
24.0 Vdc
3.3 vsb*
48.0 Vdc
3.3 vsb*
DS850-3
12.0 Vdc
3.3 vsb*
DS850-5
24.0 Vdc
3.3 vsb*
DS850-9
48.0 Vdc
3.3 vsb*
*For 5 vsb, consult marketing.
Set Point
Tolerance
±0.2%
±1%
±0.2%
±1%
±0.2%
±1%
±0.2%
±1%
±0.2%
±1%
±0.2%
±1%
Total
Regulation
±5%
±5%
±5%
±5%
±5%
±5%
±5%
±5%
±5%
±5%
±5%
±5%
Minimum
Current
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
0A
Maximum
Current
52.5 A
6.0 A
26.3 A
6.0 A
13.1 A
6.0 A
70.0 A
6.0 A
35.0 A
6.0 A
17.5 A
6.0 A
Output Ripple
P/P
120mV
50mV
240 mV
50 mV
480mV
50mV
120mV
50mV
240 mV
50 mV
480mV
50mV
Embedded Power for
Business-Critical Continuity
Rev. 05.29.08
DS650 and DS850
2 of 4




 DS650-5
Mechanical Drawing
Power Supply Condition
LED
Green/Amber
No AC power to all PSU
OFF
AC present/Standby outpus ON,
Main output OFF
Blinking Green
Power supply DC outputs ON and OK Solid Green
Main output failure (OCP, OVP, UVP) Blinking Amber
Fan Fail, OTP, Standby output OCP/UVP Solid Amber
1.58"
(40.2)
CLIP COMPRESSED
BI-COLOR LED
.638" ±.02"
(16.2 ±0.6)
.897" ±.02
(22.8 ± 0.6)
(2X)
3.30" ±.03"
(83.8 ±0.7)
Embedded Power for
Business-Critical Continuity
Rev. 05.29.08
DS650 and DS850
3 of 4
3.09"
(78.5)
.649
(16.5)
AIRFLOW DIRECTION
(3X) 3.09"
(78.5)
7.48"
(190.0)
11.0" ± .02"
(279.4 ±0.5)
.315"
(8.0)
.275"
(7.0)
SEE NOTE 3
(65.5)
(40.5)
(15.5)
3.09"
(78.5)
10.85" ±.03"
(275.5 ±0.7)
.767"
(19.5)
3.20" ±.02"
(81.3) ±0.5
1.60"
(40.7)
.142" ±.02" 1.57" ±.02"
(3.6 ±0.5) (39.9 ±0.5)
.354"
(9.0)
.236"
FULL R .256" (6.0)
(6.5)






Recommended third-party DS650-5 Datasheet






@ 2014 :: Datasheetspdf.com :: Semiconductors datasheet search & download site (Privacy Policy & Contact)