Document
Embedded Power for Business-Critical Continuity
HPS3000 Series
3000 Watts
Distributed Power Bulk Front-End
Single Output
Rev. 7.10.09_81 HPS3000 Series of 7
Special Features
• 3000 W output power • 40 W/cu-in • Optional customer provided air • 1U x 3U form factor • N+1 Redundant • Hot-swap • Internal OR-ing • 5 V housekeeping • High efficiency 89% @ 200 Vac, 100% load • Variable speed “smart fans” • One year warranty
Electrical Specifications
Input
Input range (operating): Input range (nominal): Frequency: Input fusing: Inrush current: Power factor: Harmonics: Input current: Holdup time: Leakage current: 180 - 264 Vac 90 - 140 Vac 200 Vac 110 Vac 43 to 63 Hz Internal 25 A fuses ≤40 A peak 0.97 typical Meets IEC 1000-3-2 requirements 19 A max input current 10 ms minimum 1.4 mA MOV directly after the fuse At full rated load At 240 Vac Input through Card Edge Connection on same end as DC output Both lines fused Either hot or cold start Meets EN61000-3-2 @ 50% load
Compliance
• POE Isolation • EMI Class B - EN55022, Level “A” • EN61000 Immunity
Power line transient:
Safety
• UL/cUL • CSA • China • Nemko • CB Report • CSA 22.2 60950 60950 CCC TUV 60950
Embedded Power for Business-Critical Continuity
230V ac E ffic ienc y
230 Vac Efficiency
100.00 90.00 80.00 70.00 60.00 50.00 40.00 30.00 20.00 10.00 10 20 30 40 50 60 70 80 90 100
% o f T o tal Ou tp u t Po w e r
Rev. 7.10.09_81 HPS3000 Series of 7
Output
Output rating 48 V @ 62.0 A 5 Vsb @ 3.0 A 48 V @ 29.4 A 5V @ 3 A 48 V 48 V ± 10% 5 Vsb ± 4% 3000 W maximum @ 200 Vac Input 1500 W maximum @ 110 Vac Input 48 V @ 0.0 A 5 Vsb @ 0.0 A 480 mV max P-P 100 mV max P-P ± 5% maximum 5% maximum deviation 180 - 264 Vac 90 - 140 Vac Programmable ±10% through I2C serial bus Line/load/transient when measured at output connection No derating over operating temp range No loss of regulation 48 V output 5 Vsb output Measured with a 0.1µF Ceramic and 10 µF Tantalum capacitor on any input Nominal Voltage Setting 50% load step @ 1 A/us Step load valid between 10% to 100% of output rating. Total power in 1U 19” rack is 12 KW Output to return >2000 Vac Digital sharing control 48 V output 5 Vsb output 48 V output 5 Vsb output Both PFC and output converter monitored 5 Vsb will operate under overtemperature condition. Built in hysteresis
Set point Total regulation range Rated load Minimum load Output noise
Output voltage overshoot Transient response Max units in parallel Short circuit protection Output isolation Forced load sharing Over current protection (OCP)
Up to 4 120% - 130% of rated output Per POE specs Within 10% of all shared outputs 120% to 130% 100% to 125% Over voltage protection (OVP) 110% to 120% 110% to 125% Over temperature protection 10 - 15 deg C above safe operating area
Environmental Specifications
Vibration/Shock: Operating temperature: Storage Temperature: Cooling Operating Relative Humidity: Storage Relative Humidity: Operating Altitude Storage Altitude: RoHS Compliant: .