AC-DC / Distributed Power Front End 3U
3000 Watts
HPS3KW
Input
Total Power: Input Voltage: # of Outputs:
3000 Watts 180-264 VAC Single
Electrical Specs - *M...
Description
3000 Watts
HPS3KW
Input
Total Power: Input Voltage: # of Outputs:
3000 Watts 180-264 VAC Single
Electrical Specs - *Module only
Input Range Frequency Inrush Current Efficiency EMI Filter Power Factor Leakage Current 180-264VAC 47 - 63 Hz 100A (peak) 85% typical at full load CISPR22 Class A 0.98 typical 1.16 mA @ 240 VAC
Special Features - *Module only
Active Power Factor Correction EN61000-3-2 Harmonic Compliance Remote INHIBIT Single Wire Parallel Built-in EMI Filter Low Output Ripple +5V standby Output Built-in Cooling Fans Over Current Protection Over Voltage Protection Over Temperature Protection Hot Swap Built-in OR'ing Diodes
Output
DC Voltage Adjustment Range Supervisory Output Hold Up Time Over Current Over Voltage 51.4V @ 57A* 5Vsb @ 5A ± 5% 5V @ 5A 20ms 51.4V: 110% - 150% 5Vsb: 101% - 125% 60V Max Requires contact closure from "PSON" to 5Vsb return. TTL signal LOW TTL signal LOW; goes HIGH inthe event of failure TTL logic signal goes high 1001000 msec after 48VDC output. It goes LOW at least 1ms before loss of regulation.
Logic Control
ENABLE AC OK POWER FAIL POWER GOOD
Environmental - *Module only
Operating Temperature: +5°C to 40°C Non-Operating Temperature: -40° to +70°C Electromagnetic Susceptibility: Designed to meet EN61000-4-2, -4-3, 4-4, -4-5 Level 3 Humidity: 5 to 95% RH, non-condensing Operating: Sinusoidal Vibration - 0.25G zero to peak, 10 to 500Hz, 0.25 oct/min in each three mutually perpendicular axes. Random vibration ...