Document
Advanced Digital Temperature Controller
E5AN-H/E5EN-H
(96 x 96 mm and 48 x 96 mm)
www.DataSheet4U.com
CSM_E5AN-H_E5EN-H_DS_E_3_2
A New High-performance Controller: High Resolution, High Speed, and High Input Accuracy. Logic Operations and Preventive Maintenance Function. Plus Infrared Port on Front Panel.
• High-resolution display with 5 digits/0.01°C display. • High-speed sampling cycle of 60 ms. • High Accuracy Thermocouple/Pt input: ±0.1% of PV Analog input: ±0.1% FS • Universal inputs on all models (thermocouple, PT, or analog input) to handle various sensors with one Controller. Models also available with Remote SP. • A PV/SV-status display function can be set to automatically alternate between displaying the status of the Temperature Controller (auto/manual, RUN/STOP, and alarms) and the PV or SV. • Flexible contact outputs with logic operations (AND, OR, and delays) set from the Support Software (CX-Thermo Ver. 4.0) • Preventive maintenance for relays in the Temperature Controller using a Control Output ON/OFF Counter. • Model available with position-proportional control
96 × 96 mm E5AN-H
48 × 96 mm E5EN-H
Refer to Safety Precautions for E5@N/E5@N-H. Refer to Operation for E5@N/E5@N-H for operating procedures.
Main I/O Functions
Remote SP Input • One Event Inputs • None • Two • Four Universal Sensor Inputs • Universal thermocouple/ Pt/analog (current/voltage) inputs. Indication Accuracy • Thermocouple/Pt input: ±0.1% of PV • Analog input: ±0.1% FS Sampling Period • 60 ms PF Key (Programmable key function)
E5AN-H
E5EN-H
3-level Display Simultaneously displays set items, such as the PV, SV, and MV. 5-digit Display with high resolution of 0.01°C • Auto/manual switching • Temperature Controller status display • Simple program function • Logic operations • Control output ON/OFF count alarm • PV change rate alarm • Models available with RS-485, RS-422, or RS-232C communications
Infrared port
Auxiliary Outputs • Two • Three Computer Support Software CX-Thermo
USB
Control Output 2 (built-in) Output Unit • SSR outputs • Relay output • Voltage output (for driving SSR) • Current output • Linear voltage output Control Output 1 (built-in) Output Unit • SSR outputs • Relay output • Voltage output (for driving SSR) • Current output • Linear voltage output
1
E5AN-H/E5EN-H
www.DataSheet4U.com
Lineup
1 control output
2 auxiliary outputs
E5AN-H/E5EN-H
Advanced Type
Terminal block
Fully universal input 2 control outputs
2 auxiliary outputs
Note: The Controller can be used for heating/cooling control even if only 1 control output is used.
Model Number Structure
Model Number Legend
Controllers Option Units
E5AN/E5EN-@@@@@@@M@-@-500
1 2 3 4 5 6 7 8 9 10
1. Type H: Advanced 2. Control Mode Blank: Standard or heating/cooling control P: Position-proportional control 3. Control Output 1 A: Control Output Unit R: Relay output S: SSR output 4. Control Output 2 A: Control Output Unit R: Relay output S: SSR output 5. Auxiliary Outputs 2: Two outputs 3: Three outputs 6. Option 1 Blank: None H: Heater burnout/SSR failure/Heater overcurrent detection (CT1) HH: Heater burnout/SSR failure/Heater overcurrent detection (CT2) 7. Option 2 B: Two event inputs BF: Event input + Transfer output 8. Option 3 M: Option Unit can be mounted. 9. Power Supply Voltage Blank: 100 to 240 VAC D: 24 VAC/VDC 10.Case Color Blank: Black W: Silver 11.Terminal Cover -500: With Terminal Cover
E53-@
1
1. Function EN01: RS-232C communications EN02: RS-422 communications EN03: RS-485 communications AKB: Event input
11
Output Units
E53-@@
1 2
1. Control Output R: Relay output Q: Voltage output (for driving SSR) Q3: Voltage output (for driving SSR) + 24 VDC (NPN) Q4: Voltage output (for driving SSR) + 24 VDC (PNP) C3: Current output + 4 to 20 mA DC C3D: Current output + 0 to 20 mA DC V34: Linear voltage output + 0 to 10 VDC V35: Linear voltage output + 0 to 5 VDC 2. Version Blank: Available for E5AN-E5EN-H and E5AK/E5EK. N: Available only for E5AN-H/E5EN-H.
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions and other information required for operation before attempting to use the product. E5CN-H/E5AN-H/E5EN-H Digital Controllers User's Manual Advanced Type (Cat. No. H157) E5CN-H/E5AN-H/E5EN-H Digital Controllers Communications Manual Advanced Type (Cat. No. H159)
2
E5AN-H/E5EN-H
www.DataSheet4U.com
Ordering Information
E5AN-H
Size Case color Power supply voltage Control Auxiliary method output Control output 1/2 Control Output Unit × 2 SSR outputs × 2 2 Control Output Unit × 2 Basic 100 to 240 VAC 3 SSR outputs × 2 Relay outputs × 2 Valve Black Control Output Unit × 2 1/4 DIN 96 × 96 × 78 (W × H × D) Basic 24 VAC/ VDC 3 SSR outputs × 2 Relay outputs × 2 Valve 2 Relay outputs × 2 Control Output Unit × 2 Basic 2 Control Output Unit × 2 Control Output Unit × 2 1 2 1 2 2 2 2 2 2 SSR outputs × 2 Control Output Unit × 2 2 2 2 SSR outputs × 2 2 Control.