DIESEL ENGINE-GENERATOR SET
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 100-JC6DT3 100 ekW 60 Hz Standby
/ / 90 ekW / 60 Hz / Prime
208 ...
Description
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 100-JC6DT3 100 ekW 60 Hz Standby
/ / 90 ekW / 60 Hz / Prime
208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 240V** 1 1.0 60 100 100 417 108 431CSL6202 130°C/27°C
12 LEAD ZIG-ZAG
240V** 1 1.0 60 100 100 417 311 363CSL1617 130°C/27°C 4 LEAD
208V** 3 0.8 60 100 125 347 205 362CSL1606 130°C/27°C
12 LEAD LOW WYE
240V** 3 0.8 60 100 125 301 205 362CSL1606 130°C/27°C
12 LEAD HI DELTA
480V** 3 0.8 60 100 125 150 230 362CSL1606 130°C/27°C 12 LEAD HI WYE
600V** 3 0.8 60 100 125 120 270 362PSL1636 125°C/40°C 4 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 240V 1 1.0 60 90 90 375 108 431CSL6202 105°C/40°C
12 LEAD ZIG-ZAG
240V 1 1.0 60 90 90 375 311 363CSL1617 105°C/40°C 4 LEAD
208V 3 0.8 60 90 112.5 312 205 362CSL1606 105°C/40°C
12 LEAD LOW WYE
240V 3 0.8 60 90 112.5 271 205 362CSL1606 105°C/40°C
12 LEAD HI DELTA
480V 3 0.8 60 90 112.5 135
600V 3 0.8 60 90 112.5 108
270 270 362CSL1606 362PSL1636 105°C/40°C 105°C/40°C 12 LEAD HI WYE 4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered