DIESEL ENGINE-GENERATOR SET 200-JC6DT3 200 ekW 60 Hz Standby
/ / 180 ekW / 60 Hz / Prime
208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 240V** 1 1.0 60 200 200 833 250 432CSL6212 130°C/27°C
12 LEAD ZIG-ZAG
240V** 1 1.0 60 200 200 833 370 432PSL6228 130°C/27°C 4 LEAD
208V** 3 0.8 60 200 250 694 370 431CSL6206 130°C/27°C
12 LEAD LOW WYE
240V** 3 0.8 60 200 250 601 370 431CSL6206 130°C/27°C
12 LEAD HI DELTA
480V** 3 0.8 60 200 250 301 495 431CSL6206 130°C/27°C 12 LEAD HI WYE
600V** 3 0.8 60 200 250 241 510 431PSL6243 125°C/40°C 4 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 240V 1 1.0 60 180 180 750 250 432CSL6212 105°C/40°C
12 LEAD ZIG-ZAG
240V 1 1.0 60 180 180 750 370 432PSL6228 105°C/40°C 4 LEAD
208V 3 0.8 60 180 225 625 370 431CSL6206 105°C/40°C
12 LEAD LOW WYE
240V 3 0.8 60 180 225 541 370 431CSL6206 105°C/40°C
12 LEAD HI DELTA
480V 3 0.8 60 180 225 271 495 431CSL6206 105°C/40°C 12 LEAD HI WYE
600V 3 0.8 60 180 225 217 510 431PSL6243 105°C/40°C 4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered
2
// / /
200-JC6DT3
Facts
// // // // // // // // // //
EPA Tier 3 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response UL2200, CSA Listing Offered Accepts Rated Load in One Step Per NFPA 110, Level 1 All engine-generator sets are prototype and factory tested MTU Onsite Energy is a single source supplier Global Product Support 2 Year Standard Warranty Custom Design for Any Application 6068HF485 Diesel Engine - 6.8 Liter Displacement - 4-Cycle
// //
//
//
Complete Range of Accessories Permanent Magnet Generator (PMG) - Optional - Brushless, Rotating Field - 300% Short Circuit Capability - 2/3 Pitch Windings Digital Control Panel(s) - UL Recognized, , NFPA 110 - Complete System Metering - LCD Display Cooling System - Integral Set-Mounted - Engine Driven Fan
STANDARD EQUIPMENT
//
Engine
Brushless Alternator with Brushless Pilot Exciter 4 Pole, Rotating Field 130°C Standby Temperature Rise 1 Bearing, Sealed Flexible Coupling Full Amortisseur Windings 125% Rotor Balancing 3-Phase Voltage Sensing ±1% Voltage Regulation 100% of Rated Load - One Step 3% Maximum Harmonic Content
Air Cleaners Oil Pump Full Flow Oil Filter Jacket Water Pump Inter Cooler Water Pump Thermostat Exhaust Manifold – Dry Blower Fan & Fan Drive Radiator - Unit Mounted Electric Starting Motor - 12V Governor – Electric Isochronous Base - Formed Steel SAE Flywheel & Bell Housing Charging Alternator - 12V Battery Box & Cables Flexible Fuel Connectors.