Document
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 2800-XC6DT2 2800 ekW 60 Hz Standby
/ / 2500 ekW / 60 Hz / Prime
480 - 13.8kV
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 480V** 3 0.8 60 2800 3500 4210 5200 1020FDL1004 130°C/27°C 6 LEAD WYE 600V 3 0.8 60 2800 3500 3368 5900 1020FDS1014 125°C/40°C 6 LEAD WYE 4160V 3 0.8 60 2800 3500 486 C/F 1020FDM1211 130°C/27°C 6 LEAD WYE 12470V 3 0.8 60 2800 3500 162 C/F 1030FDH1428 130°C/27°C 6 LEAD WYE 13200V 3 0.8 60 2800 3500 153 C/F 1030FDH1428 130°C/27°C 6 LEAD WYE 13800V 3 0.8 60 2800 3500 146 C/F 1030FDH1428 130°C/27°C 6 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 480V 3 0.8 60 2500 3212.5 3864 5200 1020FDL1004 105°C/40°C 6 LEAD WYE 600V 3 0.8 60 2500 3212.5 3091 5900 1020FDS1014 105°C/40°C 6 LEAD WYE 4160V 3 0.8 60 2500 3212.5 446 C/F 1020FDM1211 105°C/40°C 6 LEAD WYE 12470V 3 0.8 60 2500 3212.5 149 C/F 1030FDH1428 105°C/40°C 6 LEAD WYE 13200V 3 0.8 60 2500 3212.5 141 C/F 1030FDH1428 105°C/40°C 6 LEAD WYE 13800V 3 0.8 60 2500 3212.5 134 C/F 1030FDH1428 105°C/40°C 6 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered
2
// / /
2800-XC6DT2
Facts
// // // // // // // // // //
EPA Tier 2 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response UL2200, CSA Listing Offered Accepts Rated Load in One Step Per NFPA 110, Level 1 All engine-generator sets are prototype and fatory tested MTU Onsite Energy is a single source supplier Global Product Support 2 Year Standard Warranty Custom Design for Any Application 20V 4000 G83 Diesel Engine - 95.4 Liter Displacement - Common Rail Injection - 4-Cycle
// //
//
//
Complete Range of Accessories Permanent Magnet Generator (PMG) - Brushless, Rotating Field - 300% Short Circuit Capability - 2/3 Pitch Windings Digital Control Panel(s) - UL Recognized, , NFPA 110 - Complete System Metering - LCD Display Cooling System - Integral Set-Mounted - Engine Driven Fan
STANDARD EQUIPMENT
//
Engine
Brushless Alternator with Brushless Pilot Exciter 4 Pole, Rotating Field 130°C Standby Temperature Rise 2 Bearing, Sealed Flexible Coupling Full Amortisseur Windings 125% Rotor Balancing 3-Phase Voltage Sensing ±.25% Voltage Regulation 100% of Rated Load - One Step 3% Maximum Harmonic Content
Air Cleaners Oil Pump Full Flow Oil Filter Jacket Water Pump Inter Cooler Water Pump Thermostats Exhaust Manifold – Dry Blower Fan & Fan Drive Radiator - Unit Mounted Electric Starting Motor - 24V Governor – Electric Isochronous Base - Structural Steel SAE Flywheel & Bell Housing Charging Alternator - 24V Battery Box & Cables Flexible Fuel Connectors Flexible Exhaust Connection EPA Certified Engine
//
Digital Control Panel(s)
//
Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise and motor starting www.DataSheet4U.com Sustained short circuit current of up to 300% of the rated current for up to 10 seconds Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full Load Regulation
Digital Metering Engine Parameters Generator Protection Functions Engine Protection SAE J1939 Engine ECU Communications Windows-Based Software Multilingual Capability Remote Communications to our RDP-110 Remote Annunciator 16 Programmable Contact Inputs 7 Contact Outputs UL Recognized, , CE Approved Event Recording IP 54 Front Panel Rating with Integrated Gasket NFPA110 Level Compatible
3
// / /
2800-XC6DT2
Application data
//
Engine
MTU Detroit Diesel 20V4000 G83 4-Cycle 20V 5,822 (95.4) 6.69 (17) 8.27 (21) 16.5:1 1,800 ADEC 4,035 (3,010) 3,673 (2,740) ±.25% 60 Hz Dry
//
Fuel Consumption
STANDBY 195 (738) 149 (564) 103 (390) PRIME 177 (670) 138 (522) 96 (363)
Manufacturer Model Type Arrangement Displacement: Cu In (lit) Bore: in (cm) Stroke: in (cm) Compression Ratio Rated RPM Engine Governor Max Power: Standby: bhp (kWm) Max Power: Prime: bhp (kWm) Regulation Frequency Air Cleaner
At 100% of Power Rating: gal/hr (lit/hr) At 75% of Power Rating: gal/hr( lit/hr) At 50% of Power Rating: gal/hr (lit/hr)
//
Cooling - Radiator System
//
Liquid Capacity (Lubrication)
103 (390) 54.2 (205) 14.5 (55) 215 (814)
STANDBY PRIME Ambient Capacity of Radiator: °F (°C) 118 (48) 118 (48) Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa) 0.5 (0.12) 0.5 (0.12) Water Pump Capacity: gpm (lit/min) 440 (1,667) 440 (1,667) After Cooler Pump Capacity: gpm (lit/min) 163 (617) 163 (617) Heat Rejection to Coolant: BTUM (kW) 67,675 (1,190) 60,282 (1.