Document
A tognum Group Brand
GAS Engine-Generator Set 40-GC6NLT1 40 ekW 60 Hz Standby
/ /
208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz Natural Gas Ratings: Amps Natural Gas Ratings: kW/kVA LP Gas Ratings: Amps LP Gas Ratings: kW/kVA skVA@30% Voltage Dip Generator Model* Temp Rise Connection 240V** 1 1.0 60 146 35/35 167 40/40 128 362CSL1604 130°C/27°C
12 LEAD ZIG-ZAG
240V** 1 1.0 60 146 35/35 167 40/40 102 284CSL1550 125°C/40°C
4 LEAD
208V** 3 0.8 60 139 40/50 139 40/50 93 284CSL1542 130°C/27°C
12 LEAD LOW WYE
240V** 3 0.8 60 120 40/50 120 40/50 93 284CSL1542 130°C/27°C
12 LEAD HI DELTA
480V** 3 0.8 60 60 40/50 60 40/50 133 284CSL1542 130°C/27°C
12 LEAD HI WYE
600V** 3 0.8 60 48 40/50 48 40/50 92 361PSL1632 125°C/40°C
4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered
Facts
Engine-Generator Set Tested to ISO 8528-5 for Transient Response // UL2200, CSA Listing Offered // Accepts Rated Load in One Step Per NFPA 110, Level 1 // All engine-generator sets are prototype and factory tested // MTU Onsite Energy is a single source supplier // Global Product Support // 2 Year Standard Warranty // Custom Design for Any Application // 4.3 L Engine www.DataSheet4U.com - 4.3 Liter Displacement - 4-Cycle // Integral Vibration Isolators
// // //
//
//
Complete Range of Accessories Permanent Magnet Generator (PMG) - Optional - Brushless, Rotating Field - 300% Short Circuit Capability - 2/3 Pitch Windings Digital Control Panel(s) - UL Recognized, , NFPA 110 - Complete System Metering - LCD Display Cooling System - Integral Set-Mounted - Engine Driven Fan
2
// / /
40-GC6NLT1
STANDARD EQUIPMENT
//
Engine
//
Digital Control Panel(s)
Air Cleaner Oil Pump Full Flow Oil Filter Jacket Water Pump Thermostat Exhaust Manifold – Dry Blower Fan & Fan Drive Radiator - Unit Mounted Electric Starting Motor - 12V Governor – Electric Isochronous Base - Formed Steel SAE Flywheel & Bell Housing Charging Alternator - 12V Battery Box & Cables Flexible Fuel Connectors Flexible Exhaust Connection EPA Certified Engine
Digital Metering Engine Parameters Generator Protection Functions Engine Protection SAE J1939 Engine ECU Communications Windows-Based Software Multilingual Capability Remote Communications to our RDP-110 Remote Annunciator 16 Programmable Contact Inputs 7 Contact Outputs UL Recognized, , CE Approved Event Recording IP 54 Front Panel Rating with Integrated Gasket NFPA110 Level Compatible
//
Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise and motor starting Sustained short circuit current of up to 300% of the rated current for up to 10 seconds Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full L.