DIESEL ENGINE-GENERATOR SET
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 400-XC6DT3 400 ekW 60 Hz Standby
/ / 340 ekW / 60 Hz / Prime
208...
Description
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 400-XC6DT3 400 ekW 60 Hz Standby
/ / 340 ekW / 60 Hz / Prime
208 - 4160V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 240V** 1 1.0 60 400 400 1667 700 573RSL4035 130°C/27°C
12 LEAD ZIG-ZAG
208V** 3 0.8 60 400 500 1388 820 433CSL6220 130°C/27°C
12 LEAD LOW WYE
240V** 3 0.8 60 400 500 1203 820 433CSL6220 130°C/27°C
12 LEAD HI DELTA
480V** 3 0.8 60 400 500 601 1100 433CSL6220 130°C/27°C 12 LEAD HI WYE
600V** 3 0.8 60 400 500 481 1100 433PSL6248 125°C/40°C 4 LEAD WYE
4160V 3 0.8 60 400 500 69 1100 573FSM4352 130°C/27°C 6 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 240V 1 1.0 60 340 340 1417 700 573RSL4035 105°C/40°C
12 LEAD ZIG-ZAG
208V 3 0.8 60 340 425 1180 820 433CSL6220 105°C/40°C
12 LEAD LOW WYE
240V 3 0.8 60 340 425 1022 820 433CSL6220 105°C/40°C
12 LEAD HI DELTA
480V 3 0.8 60 340 425 511 1100 433CSL6220 105°C/40°C 12 LEAD HI WYE
600V 3 0.8 60 340 425 409 1100 433PSL6248 105°C/40°C 4 LEAD WYE
4160V 3 0.8 60 340 425 59 1100 573FSM4352 105°C/40°C 6 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered...