DIESEL ENGINE-GENERATOR SET
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 415-JC6DT3 415 ekW 60 Hz Standby
/ / 360 ekW / 60 Hz / Prime
208...
Description
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 415-JC6DT3 415 ekW 60 Hz Standby
/ / 360 ekW / 60 Hz / Prime
208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 208V 3 0.8 60 415 518.75 1440 790 572RSL4025 130°C/27°C 12 LEAD LOW WYE 240V 3 0.8 60 415 518.75 1248 790 572RSL4025 130°C/27°C 12 LEAD HI DELTA 480V** 3 0.8 60 415 518.75 624 1100 433CSL6220 130°C/27°C 12 LEAD HI WYE 600V 3 0.8 60 400 500 481 1040 572RSS4270 125°C/40°C 4 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 208V 3 0.8 60 360 450 1249 820 572RSL4025 105°C/40°C 12 LEAD LOW WYE 240V 3 0.8 60 360 450 1083 970 572RSL4025 105°C/40°C 12 LEAD HI DELTA 480V 3 0.8 60 360 450 541 1300 433CSL6220 105°C/40°C 12 LEAD HI WYE 600V 3 0.8 60 360 450 433 1100 572RSS4270 105°C/40°C 4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered
2
// / /
415-JC6DT3
Facts
// // // // // // // // //
EPA Tier 3 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response UL2200, CSA Listing Offered Accepts Rated Load in One Step Per NFPA 110, Level 1 All engine-generator sets are prototype and factory tested MTU Onsit...