DIESEL ENGINE-GENERATOR SET
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 60-JC6DT3 60 ekW 60 Hz Standby
/ / 55 ekW / 60 Hz / Prime
208 -...
Description
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 60-JC6DT3 60 ekW 60 Hz Standby
/ / 55 ekW / 60 Hz / Prime
208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* Temp Rise Connection 240V** 1 1.0 60 60 60 250 119 362CSL1604 130°C/27°C
12 LEAD ZIG-ZAG
240V** 1 1.0 60 60 60 250 130 361CSL1613 130°C/27°C 4 LEAD
208V** 3 0.8 60 60 75 208 150 361CSL1602 130°C/27°C
12 LEAD LOW WYE
240V** 3 0.8 60 60 75 180 150 361CSL1602 130°C/27°C
12 LEAD HI DELTA
480V** 3 0.8 60 60 75 90 198 361CSL1602 130°C/27°C 12 LEAD HI WYE
600V** 3 0.8 60 60 75 72 136 361PSL1633 125°C/40°C 4 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model* www.DataSheet4U.com Temp Rise Connection 240V 1 1.0 60 55 55 229 119 362CSL1604 105°C/40°C
12 LEAD ZIG-ZAG
240V 1 1.0 60 55 55 229 130 361CSL1613 105°C/40°C 4 LEAD
208V 3 0.8 60 55 68.75 191 150 361CSL1602 105°C/40°C
12 LEAD LOW WYE
240V 3 0.8 60 55 68.75 165 150 361CSL1602 105°C/40°C
12 LEAD HI DELTA
480V 3 0.8 60 55 68.75 83 140 361CSL1602 105°C/40°C 12 LEAD HI WYE
600V 3 0.8 60 55 68.75 66 136 361PSL1633 105°C/40°C 4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration. ** UL2200 Offered
2
// / /
60-JC6DT3
Facts
// // ...