DIESEL ENGINE-GENERATOR SET
A tognum Group Brand
Diesel Engine-Generator Set 75-JS6DT3
75 ekW / 60 Hz / Standby 208 - 600V
System Ratings
Standby
...
Description
A tognum Group Brand
Diesel Engine-Generator Set 75-JS6DT3
75 ekW / 60 Hz / Standby 208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model Temp Rise Connection
** UL2200 Offered
240V** 1 1.0 60 75 75 271 127 362PSL1606 130°C/27°C 12 LEAD ZIG-ZAG
208V** 3 0.8 60 75 93.75 260 202 362PSL1606 130°C/27°C 12 LEAD LOW WYE
240V** 3 0.8 60 75 93.75 226 270 362PSL1606 130°C/27°C 12 LEAD HI DELTA
480V** 3 0.8 60 75 93.75 113 270 362PSL1606 130°C/27°C 12 LEAD HI WYE
600V** 3 0.8 60 75 93.75 90 235 362PSL1635 125°C/40°C 4 LEAD WYE
Facts
EPA Tier 3 Certified Engine-Generator Set Tested to ISO 8528-5 for Transient Response // UL2200, CSA Listing Offered // Accepts Rated Load in One Step Per NFPA 110, Level 1 // All engine-generator sets are prototype and factory tested // MTU Onsite Energy is a single source supplier www.DataSheet4U.com // Global Product Support // 2 Year Standard Warranty // 4045HF285 Diesel Engine - 4.5 Liter Displacement - 4-Cycle
// // // //
//
//
Complete Range of Accessories Permanent Magnet Generator (PMG) - Optional - Brushless, Rotating Field - 300% Short Circuit Capability - 2/3 Pitch Windings Digital Control Panel(s) - UL Recognized, , NFPA 110 - Complete System Metering - LCD Display Cooling System - Integral Set-Mounted - Engine Driven Fan
2
// / /
75-JS6DT3
STANDARD EQUIPMENT
//
Engine
...
Similar Datasheet