Solid state I/O switching modules deliver an electrically clean, photo-isolated, noise-free "output" interface from logic level control systems to external loads such as motors, valves, solenoids, etc. -- or an "input" interface from the load or sensors to microprocessor or computer-based logic level systems. Designed for long, reliable service in demanding industrial environments.
www.DataSheet4U.com
INPUT SPECIFICATIONS
IAC5 (S)MIAC 5 X4IAC5
IAC15 (S)MIAC 15 X4IAC15
IAC24 (S)MIAC 24 X4IAC24
IAC5A (S)MIAC 5A X4IAC5A
IAC15A (S)MIAC 15A X4IAC15A
IAC24A (S)MIAC 24A X4IAC24A
Nominal input voltage [Vrms/Vdc] Minimum Input Voltage [Vrms/Vdc] Maximum Input Voltage [Vrms/Vdc] Maximum Input Current [mA rms] Drop Out Current [mA rms] Allowable Off-state Current [mA rms] Allowable Off-state Voltage [Vrms/Vdc]
120 90 140 10 2.5 3.0 50.0
120 90 140 10 2.5 3.0 50.0
120 90 140 10 2.5 3.0 50.0
240 180 280 8 1.5 2.0 120
240 180 280 8 1.5 2.0 120
240 180 280 8 1.5 2.0 120
OUTPUT SPECIFICATIONS
Nominal Logic Voltage [Vdc] Minimum Logic Voltage [Vdc] (X4 Series) Maximum Logic Voltage [Vdc] (X4 Series) Typical Logic Supply Current [mAdc] Max. Logic Supply Current [mAdc] Max. Logic Sup. Leak. Current [µAdc] Maximum Output Voltage [Vdc] Maximum Output Current [mAdc] Max. Output Leakage Current [µAdc] Max. Output Voltage Drop [mVdc] Maximum Turn-on Time [msec] Maximum Turn-off Time [msec] 5 1.5 (3) 6.0 (7) 10 18.5 10 30 50 10 200 20 30 15 8.5 (10) 18.5 (20) 10 16 10 30 50 10 200 20 30 24 16.5 (18) 30.5 (32) 10 14 10 30 50 10 200 20 30 5 1.5 (3) 6.0 (7) 10 18.5 10 30 50 10 200 20 30 15 8.5 (10) 18.5 (20) 10 16 10 30 50 10 200 20 30 24 16.5 (18) 30.5 (32) 10 14 10 30 50 10 200 20 30
© 2002 CRYDOM CORP Specifications subject to change without notice.
FastFax Document No. 302 SERIES IDC. Rev. 031902 PAGE 1 OF 2
For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154 Email:
[email protected] WEB SITE: http://www.crydom.com UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email:
[email protected]. GERMANY: +49 (0)180 3000 506
Series IAC, (S)MIAC, X4IAC
AC Input Modules
GENERAL SPECIFICATIONS
Operating temperatue ranger Storage temperature range Isolation Capacitance input to output Line frequency range Package Color Ð30 to +80˚C Ð40 to +100˚C 4,000 V rms 8 pF 47 to 63 Hz Yellow
W IRING & M ECHANICAL DIAGRAMS Standard Series, IAC
BOTTOM VIEW
Standard and Mi ni Pack
1
1
X4 Series
.30 (7.6)
.60 (15.2)
Vac/dc
Vac/dc
CAPTIVE #4-40. PHILLIPS HEAD HOLD DOWN SCREW
1.70 (43.1)
1.00 (25.4)
.100 (2.5)
2
2
LOGIC
1.25 (31.7)
+
3
LOGIC
+
3
OUT
Schmitt Trigger
4
OUT
Schmitt Trigger
4
.25 (6.3)
5
4
3
2
1
.030 (0.8) .30 (7.6)
GND
5
GND
5
.040 (1.0) DIA. (5 PLACES)
.70 (17.8) 1.20 (30.5) 1.40 (35.5) 1.60 (40.6)
X4 Series, X4IAC MI NI-PACK Series, (S)MIAC
SM Prefix M Prefix
0.81 (20.6) 0.20 (5.1) CAPTIVE #4-40. PHILLIPS HEAD HOLD DOWN SCREW
APPLICATION NOTES
¥ Do not install or remove modules in live (electrically hot) circuits. High voltage may be present. ¥ An externally located commutating diode must be installed across inductive loads ¥ I/O module boards also available
.25 (6.35) .30 (7.6) .200 (5.1) .700 (17.8) 1.100 (27.9) 1.30 (43.1) 1.70 (43.1)
BOTTOM VIEW
CAPTIVE #4-40. PHILLIPS HEAD HOLD DOWN SCREW
1.70 (43.1) 1.00 (25.4)
1.70 (43.1)
1.78 (45.2)
1.00 (25.4)
1.00 (25.4)
5
4
3+
2
1
.25 (6.35) .30 (7.6)
5
4
3+
2
1
.040 (1.0) DIA. (5 PLACES)
.200 (5.1) .700 (17.8) 1.100 (27.9) 1.30 (43.1) 1.70 (43.1)
BOTTOM VIEW
1.82 (46.2)
0.48 (12.2)
.040 (1.0) DIA. (5 PLACES)
.040 (1.0) DIA. (5 PLACES)
0.15 (3.8) 0.35 (8.9) 0.55 (13.9) 0.20 (5.1) 1.3 (33.0) 1.70 (43.1)
.100 (2.5) .40 (10.2)
.40 (10.2) .100 (2.5)
All dimensions are in inches (millimeters)
© 2002 CRYDOM CORP Specifications subject to change without notice.
FastFax Document No. 302 SERIES IDC. Rev. 031902 PAGE 2 OF 2
For recommended applications and more information contact: USA: Sales Support (877) 502-5500 Tech Support (877) 702-7700 FAX (619) 710-8540 Crydom Corp, 2320 Paseo de las Americas, Ste. 201, San Diego, CA 92154 Email:
[email protected] WEB SITE: http://www.crydom.com UK: +44 (0)1202 365070 • FAX +44 (0)1202 365090 Crydom International Ltd., 7 Cobham Road, Ferndown Industrial Estate, Ferndown, Dorset BH21 7PE, Email:
[email protected]. GERMANY: +49 (0)180 3000 506
.