(SS20-xxx) AC Line Surge Suppressor
Anz195, Last Update: Jan. 23, 2013
AC Line Surge Suppressor
FEATURES:
●Integrated thermal protection device per UL1449...
Description
Anz195, Last Update: Jan. 23, 2013
AC Line Surge Suppressor
FEATURES:
●Integrated thermal protection device per UL1449 ●Designed to be used in conjunction with LED drivers, Fluorescent Ballasts ●Suitable for dry, damp and wet location applications ●Designed to meet IEEE C62.42 surge requirements ●Wide range operational temperature from -40°C - +85°C ●LED indicator for ease of maintenance ●Standard 1/2" NPT threaded for quick installation ●Compact, ergonomic shape with mounting tab
SS-20 series
Safety Approval:
IP66
SPECIFICATION:
Pending
Maximum Rating (+85°C) Continuous Transient Peak Surge C t 1TM 1 x Pulse (A) 20000 20000 20000
Specifications (25°C)
Model #
AC Volts VM(AC)RMS (V) 150 320 550 DC Volts VM(DC) (V) 200 420 715
Varistor Voltage at 1mA Test Current
Maximum Clamping Voltage 8/20µS
Energy 2ms W TM (J) 120 270 360
Typical Capacitanc e f= 1Mhz
VN(DC) Min. VN(DC) Max.
http://www.DataSheet4U.net/
VC
IPK (A) 100 100 100
C (pF) 2300 1080 630
(V) 216 459 819
SS20-120 SS20-277 SS20-480 Note: SS20-120 is designed for use in 120VAC environment SS20-277 is designed for use in 277VAC environment SS20-480 is designed for use in 480VAC environment
(V) 264 395 561 840 1001 1500 Safety Standards: UL1449 IEC61051-1 IEC61051-2
Wiring Diagram:
Mechanical Dimension:
L N G
SS-xxx
LED Driver
LOAD
Last update: Jan. 23, 2013
www.magtechind.com
THE POWER TO DRIVE INNOVATIONS
Tel: 702-364-9998
datasheet pdf - http://www.DataSheet4U.net/
...