Current Transducer
Current Transducer HXS 50-NP
For the electronic measurement of currents : DC, AC, pulsed, mixed, with a galvanic isolati...
Description
Current Transducer HXS 50-NP
For the electronic measurement of currents : DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 12.5 - 25 - 50 A
All Data are given with a R L = 10 k Ω
Electrical data
IPN IP VOUT VREF Primary nominal r.m.s. current Primary current measuring range Analog output voltage @ IP IP = 0 Internal Reference 1) - Output voltage VREF Output impedance VREF Load impedance Output load resistance Output impedance Max. output capacitive load Supply voltage (± 5 %) Current consumption @ VC = 5 V ± 50 A ± 150 A VREF ± (0.625·IP/IPN) V VREF ± 0.0125 V 2.5 ± 0.025 V typ. 200 Ω ≥ 200 kΩ ≥2 kΩ < 10 Ω <1 µF 5 V 22 mA
Features
Hall effect measuring principle Multirange current transducer
through PCB pattern lay-out
Galvanic isolation between primary Isolation test voltage 3500V Low power consumption Extremely low profile, < 11mm Single power supply +5V Fixed offset & gain Insulated plastic case recognized
according to UL 94-V0. and secondary circuit
RL ROUT CL VC IC
Accuracy - Dynamic performance data
Accuracy 2) @ IPN , TA = 25°C εL Linearity error 0 .. IPN .. 3 x IPN TCVOUT Thermal drift of VOUT @ IP = 0 TCVREF Thermal drift of VREF TCVOUT / VREF Thermal drift of VOUT / VREF @ IP = 0 TCεG Thermal drift of the gain VOM Residual voltage @ IP = 0, after an overload of 3 x IPN DC t ra Reaction time @ 10 % of IPN tr Response time @ 90 % of IPN di/dt di/dt a...
Similar Datasheet