Document
CORCOM Product Guide Power Entry Module with RFI Power Line Filter for General or Medical Applications
L Series
UL Recognized CSA Certified VDE Approved
EDL4C/EHL4C EDL1S/EHL1S
L Series
The L series power entry modules are compact units that combine a multi-function power entry module and high performance RFI filtering capabilities. They are available with either a four-voltage selector or a DPST on/off switch. Both variations can be specified with North American or European fusing capabilities and are available in either flange or snap-in mounting. These filters are UL recognized, CSA certified, and VDE approved. The L series modules offer a choice of filters for general or medical applications. EDL Models The RFI filter is for general purpose applications where line-to-line and line-to-ground noise must be controlled. The filter is designed to meet the very low leakage requirements of VDE portable equipment. They are available in three current ratings. EHL Models This medical filter provides susceptibility protection without the leakage current associated with line-to-ground capacitors. Designed to allow equipment to meet UL544 for patient care and non-patient care equipment, the EHL filter has a maximum leakage current of 2 µA at 120 VAC 60 Hz. See Appendix C for more information on medical applications and UL standards. Note: When using the models with an IEC connector, remember that the leakage current of the companion line cord, GA400, is more significant than that of the filter which may disqualify this line cord from use in patient care applications.
Voltage Selection
To change selected voltage: disconnect the power cord; open cover using a small blade screwdriver or similar tool; insert the tool into the voltage selection slot and remove wheel from unit; select desired voltage; replace wheel into unit and close cover, making sure the selected voltage appears in connector window.
Note: All models have North American or dual European fusing capability and are available in either flange or snap-in mounting.
Voltage selection slot 4-Voltage selection wheel Fuseholder Cover
118
Catalog 1654001 Revised 05-07 Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. USA Cust. Svc.: 1-800-468-2023 CORCOM Prods: 1-847-680-7400 Germany: 49-89-6089-0 www.corcom.com www.tycoelectronics.com
Free Datasheet http://www.datasheetlist.com/
CORCOM Product Guide Power Entry Module with RFI Power Line Filter for General or Medical Applications (Continued)
L Series
Electrical Schematics
DL Models (with switch)
Note 1 H Note 2 On/Off
2 (1) (2) 4 1 (1a) (2a) 3
Specifications
Maximum leakage current, each line-to-ground: EDL EHL Models Models 0.25 mA 2 µA 0.50 mA 5 µA
Neutral Ground
Cutomer Transformer Primaries
@120 VAC 60 Hz: @250 VAC 50 Hz: Hipot rating (one minute): line-to-ground line-to-line Operating frequency: Operating voltages: 1S & 1SC Suffix (fixed): 4 & 4C Suffix (selectable): Rated current: 2EDL & 2EHL 4EDL & 4EHL 6EL, 6EDL & 6EHL Switch:
Hot G
Device
1500 1450
1500 1450
Power Entry Modules
50/60 Hz 250 VAC Max. 100, 120, 220, 240 VAC
DL Models (with 4-voltage selection)
Cutomer
120V 100V 220V 240V
Transformer Primaries A B C D E F
120V 20V
Hot
Note 1
G
Note 2 On/Off
A B C D E
A B C D E F
100V
Ground
Neutral
F H
2A 4A 6A Double-insulated, rated for 10,000 operations at full load. 51 Amp inrush capability. Accepts one .25" x 1.25" fuse or two 5 x 20 mm fuses 110 [2.79] except for switch .187 [4.8] for switch
Fuse (not included):
HL Models (with switch)
Note 2 On/Off
2 (1) (2) 4 1 (1a) (2a) 3
Neutral Ground
Note 1
H
Customer Transformer Primaries
Terminals: Minimum insertion loss in dB:
Hot G
Device
HL Models (with 4-voltage selection)
120V 100V 220V 240V
Customer Transformer Primaries A B C D E F
120V 20V
Line-to-ground in 50 ohm circuit Current Frequency-MHz .15 1 5 .05 Rating EDL Models 2A 6 14 24 40 18 32 8 4A 2 6A 1 6 17 31 EHL Models 06A 3 8 15 18 Line-to-line in 50 ohm circuit
10 45 38 37 18
30 50 45 45 18
Hot
Note 1
G
Note 2 On/Off
A B C D E
A B C D E F
100V
Ground
Neutral
F H
Current Rating .05 EDL Models 2A 7 4A 6 6A 6 EHL Models 4 06A
Frequency-MHz .5 1 3 16 14 15 14 21 18 20 20 23 23 25 28
5 37 26 24 32
10 47 45 45 38
30 50 47 50 42
Note 1: Provision for dual European style fusing. Note 2: On/Off switch present only with "S" suffix. Resistor location for reference only.
119
Catalog 1654001 Revised 05-07 Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. USA Cust. Svc.: 1-800-468-2023 CORCOM Prods: 1-847-680-7400 Germany: 49-89-6089-0 www.corcom.com www.tycoelectronics.com
Free Datasheet http://www.datasheetlist.com/