SX460 AUTOMATIC VOLTAGE REGULATOR (AVR) SPECIFICATION, INSTALLATION AND ADJUSTM ENTS General description SX460 is a hal f-wave phase-controlled thyristor type Automatic Voltage Regulator (AVR) and f orms part of the excitation system for a brush-less generator. In addition to regulating the generator voltage, the A VR circuitry includes under -speed and sensing loss prote.
Manufacture

Newage International Limited

Datasheet
Download SX460 Datasheet


Newage International Limited SX460

SX460; ction features. Excitation power is deri ved directly from the generator termina ls. Positive voltage build up from resi dual levels is ensured by the use of ef ficient semiconductors in the power cir cuitry of the AVR. The AVR is linked wi th the main stator windings and the exc iter field windings to provide closed l oop control of the output voltage with load regulation of.


Newage International Limited SX460

+/- 1.0%. In addition to being powered from the main stator, the AVR also deri ves a sample voltage from the output wi ndings for voltage control purposes. In response to this sample voltage, the A VR controls the power fed to the excite r field, and hence the main field, to m aintain the machine output voltage with in the specified limits, compensating f or load, speed, te.


Newage International Limited SX460

mperature and power factor of the genera tor. A frequency measuring circuit cont inually monitors the generator output a nd provides output under -speed protect ion of the excitation system, by reduci ng the output voltage proportionally wi th speed below a pre -settable threshol d. A manual adjustment is provided for factory setting of the under frequency roll off point, (U.

Part

SX460

Description

AUTOMATIC VOLTAGE REGULATOR



Feature


SX460 AUTOMATIC VOLTAGE REGULATOR (AVR) SPECIFICATION, INSTALLATION AND ADJUSTM ENTS General description SX460 is a hal f-wave phase-controlled thyristor type Automatic Voltage Regulator (AVR) and f orms part of the excitation system for a brush-less generator. In addition to regulating the generator voltage, the A VR circuitry includes under -speed and sensing loss prote.
Manufacture

Newage International Limited

Datasheet
Download SX460 Datasheet




 SX460
SX460 AUTOMATIC VOLTAGE
REGULATOR (AVR)
SPECIFICATION, INSTALLATION AND ADJUSTMENTS
General description
SX460 is a half-wave phase-controlled thyristor type
Automatic Voltage Regulator (AVR) and forms part of the
excitation system for a brush-less generator.
In addition to regulating the generator voltage, the AVR
circuitry includes under -speed and sensing loss protection
features. Excitation power is derived directly from the
generator terminals.
Positive voltage build up from residual levels is ensured by
the use of efficient semiconductors in the power circuitry of
the AVR.
The AVR is linked with the main stator windings and the
exciter field windings to provide closed loop control of the
output voltage with load regulation of +/- 1.0%.
In addition to being powered from the main stator, the AVR
also derives a sample voltage from the output windings for
voltage control purposes. In response to this sample
voltage, the AVR controls the power fed to the exciter field,
and hence the main field, to maintain the machine output
voltage within the specified limits, compensating for load,
speed, temperature and power factor of the generator.
A frequency measuring circuit continually monitors the
generator output and provides
output under -speed
protection of the excitation system, by reducing the output
voltage proportionally with speed below a pre -settable
threshold. A manual adjustment is provided for factory
setting of the under frequency roll off point, (UFRO). This
can easily be changed to 50 or 60 Hz in the field by push -
on link selection.
Provision is made for the connection of a remote voltage
trimmer, allowing the user fine control of the generator's
output.
Technical specification
INPUT
Voltage
Frequency
Phase
Jumper selectable
95-132V ac or
190-264V ac
50-60 Hz nominal
1
OUTPUT
Voltage
Current
Resistance
max 90V dc at 207V ac input
continuous 4 A dc
Intermittent 6 A for 10 secs
15 ohms minimum
REGULATION
+/- 1.0% (see note 1)
THERMAL DRIFT
0.05% per deg. C change in AVR ambient (note 2)
TYPICAL SYSTEM RESPONSE
AVR response
Filed current to 90%
Machine Volts to 97%
20 ms
80 ms
300 ms
EXTERNAL VOLTAGE ADJUSTMENT
+/-10% with 1 k ohm 1 watt trimmer (see note 3)
UNDER FREQUENCY PROTECTION
Set point
95% Hz (see note 4)
Slope
170% down to 30 Hz
UNIT POWER DISSIPATION
10 watts maximum
BUILD UP VOLTAGE
4 Volts @ AVR terminals
ENVIRONMENTAL
Vibration
20-100 Hz
100Hz – 2kHz
Operating temperature
Relative Humidity 0-70°C
Storage temperature
50mm/sec
3.3g
-40 to +70°C
95% (see note 5)
-55 to +80°C
NOTES
1. With 4% engine governing
2. After 10 minutes.
3. Applies to Mod status F onwards. Generator de-rate may
apply. Check with factory.
4. Factory set, semi-sealed, jumper selectable
5. Non condensing.
TD_SX460.GB_04.05_05_GB
http://www.Datasheet4U.com




 SX460
DESIGN DETAIL
Generator
Voltage
Sensing
Potential
Divider &
Rectifier
Hand
Trimmer
Low Hz
Detection
Reference
Voltage
Amp
Stability
Circuit
Synchronising
Ciruit
Ramp
Generator
Low Pass
Filter
Power
supply
Level
Detector &
Driver
Suppression
Power
Control
Devices
Exciter
Field
The main functions of the AVR are:
Potential Divider and Rectifier takes a proportion of the
generator output voltage and attenuates it. This input
chain of resistors includes the range potentiometer and
hand trimmer which adjust the generator voltage. A
rectifier converts the a.c. into d.c. for further processing.
The Amplifier (Amp) compares the sensing voltage to the
Reference Voltage and amplifies the difference (error) to
provide a controlling signal for the power devices. The
Ramp Generator and Level Detector and Driver infinitely
control the conduction period of the Power Control
Devices and hence provides the excitation system with the
required power to maintain the generator voltage within
specified limits.
The Stability Circuit provides adjustable negat ive ac
feedback to ensure good steady state and transient
performance of the control system.
The Low Hz Detector measures the period of each
electrical cycle and causes the reference voltage to be
reduced approximately linearly with speed below a
presettable threshold. A Light Emitting Diode gives
indication of underspeed running.
The Synchronising circuit is used to keep the Ramp
Generator and Low Hz Detector locked to the
generator waveform period.
The Low Pass Filter prevents distorted waveforms
affecting the operation of the AVR.
Power Control Devices vary the amount of exciter field
current in response to the error signal produced by the
Amplifier.
Suppression components are included to prevent sub
cycle voltage spikes damaging the AVR component s
and also to reduce the amount of conducted noise on
the generator terminals.
The Power Supply provides the required voltages for
the AVR circuitry.
TD_SX460.GB_04.05_05_GB




 SX460
FITTING AND OPERATING
REFER TO GENERATOR WIRING DIAGRAM
FOR CONNECTION DETAILS
F2 F1 6 7 8
VOLTS
Remove link to connect a remote voltage trim mer
Link for 110V/120V AVR input
SX460
UFRO ( Under Frequency Roll Off)
INDICATOR LED
FREQUENCY
SELECTION
STABILITY
CONTROL
SUMMARY OF AVR CONTROLS
FUNCTION
DIRECTION
VOLTS
STABILITY
UFRO
TO ADJUST GENERATOR OUTPUT VOLTAGE
TO PREVENT VOLTAGE HUNTING
TO SET THE UFRO KNEE POINT
ADJUSTMENT OF AVR CONTROLS
CLOCKWISE INCREASES OUTPUT VOLTAGE
CLOCKWISE INCREASE THE DAMPING EFFECT
CLOCKWISE REDUCES THE KNEE POINT
FREQUENCY
VOLTAGE ADJUSTMENT
The generator output voltage is set at the factory, but can
be altered by careful adjustment of the VOLTS control on
the AVR board, or by the external hand trimmer if fitted.
Terminals 1 and 2 on the AVR will be fitted with a shorting
link if no hand trimmer is required. Terminals 3 and 4 are
linked only for special low voltage applications.
CAUTION Do not increase the voltage above the rated
generator voltage. If in doubt, refer to the rating plate
mounted on the generator case.
CAUTION Do not ground any of the hand trimmer
terminals as these could be above earth potential. Failure
to observe this could cause equipment damage.
If a replacement AVR has been fitted or re -setting of the
VOLTS adjustment is required, proceed as follows:
CAUTION
1. Before running generator, turn the VOLTS control
fully anti-clockwise.
2. Turn remote volts trimmer (if fitted) to midway
position.
3. Turn STABILITY control to midway position.
4. Connect a suitable voltmeter (0 -300V ac) across line
to neutral of the generator.
5. Start generator set, and run on no load at nominal
frequency e.g. 50-53Hz or 60-63Hz.
6. If the red Light Emitting Diode (LED) is illuminated,
refer to the Under Frequency Roll Off (UFRO)
adjustment.
7. Carefully turn VOLTS control clockwise until rated
voltage is reached.
8. If instability is present at rated vo
ltage, refer to
stability adjustment, then re-adjust voltage if necessary.
9. Voltage adjustment is now completed.