A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 1750-XC6DT2 1750 ekW 60 Hz Standby
/ / 1600 ekW / 60 Hz / Prime
480 - 4160V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30%
Voltage Dip Generator Model* Temp Rise Connection 480V** 3 0.
8 60 1750 2187.
5 2631 4700 743RSL4052 130°C/27°C 4 BAR WYE 600V** 3 0.
8 60 1750 2187.
5 2105 3600 744RSS4292 125°C/40°C 4 LEAD WYE 4160V 3 0.
8 60 1750 2187.
5 304 4000 743FSM4370 130°C/27°C 6 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30%
Voltage Dip Generator Model* com Temp Rise Connection 480V 3 0.
8 60 1600 2000 2406 4700 743RSL4052...