A tognum Group Brand
Diesel Engine-Generator Set 40-JS6DT3
40 ekW / 60 Hz / Standby 208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30%
Voltage Dip Generator Model Temp Rise Connection
** UL2200 Offered
240V** 1 1.
0 60 40 40 167 63 361CSL1601 130°C/27°C 12 LEAD ZIG-ZAG
208V** 3 0.
8 60 40 50 139 105 361CSL1601 130°C/27°C 12 LEAD LOW WYE
240V** 3 0.
8 60 40 50 120 105 361CSL1601 130°C/27°C 12 LEAD HI DELTA
480V** 3 0.
8 60 40 50 60 140 361CSL1601 130°C/27°C 12 LEAD HI WYE
600V** 3 0.
8 60 40 50 48 92 361CSL1632 125°C/40°C 4 LEAD WYE
Facts