A tognum Group Brand
DIESEL ENGINE-GENERATOR SET 600-VC6DT2 600 ekW 60 Hz Standby
/ / 550 ekW / 60 Hz / Prime
208 - 4160V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30%
Voltage Dip Generator Model* Temp Rise Connection 208V** 3 0.
8 60 600 750 2082 1750 573RSL4033 130°C/27°C 12 LEAD LOW WYE 240V** 3 0.
8 60 600 750 1804 1750 573RSL4033 130°C/27°C 12 LEAD HI DELTA 480V** 3 0.
8 60 600 750 902 1450 572RSL4031 130°C/27°C 12 LEAD HI WYE 600V** 3 0.
8 60 600 750 722 1450 572RSS4272 125°C/40°C 4 LEAD WYE 4160V 3 0.
8 60 600 750 104 1550 574FSM4356 130°C/27°C 6 LEAD WYE
Prime
Voltage (L-L) Phase PF Hz kW kVA ...