www.DataSheet4U.com Industrial Power Su pplies TCL Series, 24–120 Watt Featur es ◆ For Industrial, Office and Resi dential Application UL 60950 UL 508C Ultracompact Plastic Housing ◆ Con nection by Cage Clamps Terminals or plu gable Screw Terminals ◆ ◆ ◆ ◆ ◆ ◆ ◆ ◆ ◆ ◆ NEW◆ ◆ Rel iable snap-on Mounting on DIN-Rails Ada ptor for Wall Mounting Universal Input 85-264 VAC, 5.
Manufacture

TRACO Electronic

Datasheet
Download TCL-REM240 Datasheet


TRACO Electronic TCL-REM240

TCL-REM240; 0/60 Hz Models with 5, 12, 24 and 48 VDC Output Output Voltage adjustable Power Good Signal Low Ripple and Noise Overl oad and Short-Circuit Protection Parall el Operation possible Worldwide Safety Approvals Redundancy Module 3 Year Prod uct Warranty The TRACOPOWER TCL series are a family of DIN-Rail power supplie s with an excellent price/performance r atio. With tightly.


TRACO Electronic TCL-REM240

regulated output voltage and high immun ity against electrical disturbances on the mains they provide a reliable power source for sensitive loads in industri al process controls, machine tools and other DataSheet4U.com ataShee equipment exposed to a difficult industrial env ironment. Compact size, light weight, D easy snap-on mounting on DIN-rails and the choice of two c.


TRACO Electronic TCL-REM240

onnection terminal versions are other fe atures of these power supplies. The TCL series complies with all mayor safety standards for Europe (EN60950, EN50178) , North America (UL/ cUL60950, UL508C l isted) or elsewhere in the world (with CB-Report IEC60950). Models Ordercode TCL 024-105 TCL 024-112 TCL 024–124 T CL 060–112 TCL 060–124 TCL 060–14 8 TCL 120–112 TCL 120–124 .

Part

TCL-REM240

Description

Industrial Power Supplies



Feature


www.DataSheet4U.com Industrial Power Su pplies TCL Series, 24–120 Watt Featur es ◆ For Industrial, Office and Resi dential Application UL 60950 UL 508C Ultracompact Plastic Housing ◆ Con nection by Cage Clamps Terminals or plu gable Screw Terminals ◆ ◆ ◆ ◆ ◆ ◆ ◆ ◆ ◆ ◆ NEW◆ ◆ Rel iable snap-on Mounting on DIN-Rails Ada ptor for Wall Mounting Universal Input 85-264 VAC, 5.
Manufacture

TRACO Electronic

Datasheet
Download TCL-REM240 Datasheet




 TCL-REM240
www.DataSheet4U.com
Industrial Power Supplies
TCL Series, 24–120 Watt
Features
For Industrial, Office and Residential
Application
UL 60950
UL 508C
Ultracompact Plastic Housing
Connection by Cage Clamps Terminals
or plugable Screw Terminals
Reliable snap-on Mounting on DIN-Rails
Adaptor for Wall Mounting
Universal Input 85-264 VAC, 50/60 Hz
Models with 5, 12, 24 and 48 VDC Output
Output Voltage adjustable
Power Good Signal
Low Ripple and Noise
Overload and Short-Circuit Protection
Parallel Operation possible
Worldwide Safety Approvals
NEWRedundancy Module
3 Year Product Warranty
The TRACOPOWER TCL series are a family of DIN-Rail power supplies with an ex-
cellent price/performance ratio. With tightly regulated output voltage and high im-
munity against electrical disturbances on the mains they provide a reliable power
sourcDeaftoarSsheenseitti4veUl.ocaodms in industrial process controls, machine tools and other
equipment exposed to a difficult industrial environment. Compact size, light weight,
DataShee
easy snap-on mounting on DIN-rails and the choice of two connection terminal
versions are other features of these power supplies. The TCL series complies with
all mayor safety standards for Europe (EN60950, EN50178), North America (UL/
cUL60950, UL508C listed) or elsewhere in the world (with CB-Report IEC60950).
Models
Ordercode
Input Voltage
Range
TCL 024-105
TCL 024-112
TCL 024–124
TCL 060–112
TCL 060–124
TCL 060–148
TCL 120–112
TCL 120–124
TCL 024–124C
TCL 060–112C
85 –264 VAC
Universal Input
50 / 60 Hz
TCL 060–124C
TCL 060–148C
TCL 120–112C
TCL 120–124C
DataSheet4U.com
http://www.tracopower.com
Output Power
max.
24 W
60 W
120 W
24 W
60 W
120 W
*Output Voltage
nom.
5.1 VDC
12 VDC
24 VDC
12 VDC
24 VDC
48 VDC
12 VDC
24 VDC
24 VDC
12 VDC
24 VDC
48 VDC
12 VDC
24 VDC
*Output adjustable
Output Current
max.
4.0 A
2.0 A
1.0 A
4.0 A
2.5 A
1.25 A
8.0 A
5.0 A
1.0 A
4.0 A
2.5 A
1.25 A
8.0 A
5.0 A
Connection
Detachable Screw
Terminal Block
Cage-Clamps
Page 1 of 5
DataSheet4 U .com




 TCL-REM240
www.DataSheet4U.com
Industrial Power Supplies
TCL Series
24–120 Watt
Input Specifications
Input voltage range
output derating at operation between 85...93VAC/85...130VDC:
85...264 VAC / 85...375 VDC
15% for TCL 060 & TCL 120 models
20% for TCL 024-112 & TCL 024-124
30% for TCL 024-105
Input frequency
47 – 63 Hz
Harmonic limits
EN610000-3-2 Class A
Input current at full load (typ.)
TCL 24 models:
TCL 60 models:
TCL 120 models:
115 VAC
0.35 A
1.2 A
2.0 A
230 VAC
0.2 A
0.6 A
1.0 A
Recommended circuit breaker (characteristic C or slow blow fuse)
5.0 A
Output Specifications
Output voltage adj. range
(pot.meter on frontpanel)
Output regulation (10 to 90% load variation)
Ripple and Noise (20MHz Bandwidth)
Electronic short circuit protection
Parallel operation
et4U.com Overvoltage protection, triggerpoint
Hold-up time
Power good signal (TCL 60 & TCL 120 only)
5.1 VDC model:
12 VDC models:
24 VDC models:
48 VDC models:
5.0 – 5.25 VDC
12 – 15 VDC (12 - 16 VDC for TCL 024-112)
24 – 28 VDC
48 – 56 VDC
2.5% (1% for TCL 60-112)
< 50 mV pk-pk
current limitation at 120 % typ
(constant current, automatic recovery
TCL 24 models: foldback, automatic recovery)
DataShee5t.41UV.DcCommodel:
12 / 24 VDC models:
48 VDC models:
output current characteristic suitable for
parallel operation of max. 5 units
< 6.5 VDC
< 40 VDC
< 60 VDC
115 VAC
min. 15 ms
230 VAC
min. 125 ms
12 VDC models:
24 VDC models:
48 VDC models:
trigger
point
>11V
>22V
>44V
output signal
(reference to – Vout)
11.0 V ±1.0V / 60 mA max.
22.0 V ±2.0V / 30 mA max.
44.0 V ±4.0V / 15 mA max.
DataShee
General Specifications
Temperature ranges
– Operating
– Storage (non operating)
– 10 °C…+70 °C max.
– 25 °C…+85 °C
Temperature derating
at 187...264 VAC or 265...375 VDC operation
at 93...132 VAC or 130...187 VDC operation
at 85...130 VDC operation
1.7% /K above 50°C
1.1% /K above 40°C
1.3% /K above 30°C
Humidity (non condensing)
95 % rel. H max.
Temperature coefficient
0.02 % /K
Switching frequency
55 – 180 kHz depending on load
(frequency modulation)
Efficiency
88% typ.
Isolation
according to IEC/EN 60950, UL 60950,
UL 508, EN 50178, EN 60204, EN 61558-2-8
Reliability, calculated MTBF @ 25°C
(according to IEC-1709)
TCL 24 models: >2.68 Mio h
TCL 60 models: >2.94 Mio h
TCL 120 models: >1.62 Mio h
DataSheeAt4ll Usp.eccoifimcations valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
http://www.tracopower.com
Page 2 of 5
DataSheet4 U .com




 TCL-REM240
www.DataSheet4U.com
General Specifications
Safety standards
Safety approvals (TCL 24 models pending)
Electromagnetic compatibility (EMC), Emissions
Electromagnetic compatibility (EMC), Immunity
Safety class
Case protection
Enclosure material
Mounting
Options
TCL–REM240 Redundancy Module
Industrial Power Supplies
TCL Series
24–120 Watt
IEC 60950, EN 60950 (output SELV),
UL 60950, UL 508, EN 50178,
EN 60204, EN 61558-2-8.
- NEC class 2 (TCL 60 models only)
UL/cUL 60950 recognized, File E181381
UL 508C listed, File E210002
CB-Report per IEC 60950
EN 61000-6-3
EN 61000-6-2
degree of protection class 1
IP 20 (IEC 60529)
plastic FR2010-110C (UL 94V-0 rated)
35 mm DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
Adapter for Wall-/Chassi Mounting (included)
output characteristic optimized for battery
charging available on request
This module enables redundant operation of any two TCL models by decoupling
the 2 power supplies. It can also be used to separate sensitive loads from the main
et4U.com power source.
DataSheet4U.com
DataShee
Models
Order code
TCL–REM240
Inputs
Vin
2 x 5...60 VDC
Specifications
Operating temperature
Electromagnetic compatibility
Dimensions
Max power
per input
144 W
Output voltage
Vin – 0.9 VDC
Output current
max.
8A
Connection
detachable screw
terminal block
– 10°C...+70°C max. (14°F...+158°F)
derating above 40°C (104°F): 1.5%/K
in correspondence to connected units
(no internal switching device)