Description General Purpose Fuses
Feature NON; NON/NOS, 600/250Vac Class K5 & H NON (250V) 1⁄8-600A, General Purpose Fuses Description: Basic pro.
Manufacture Cooper
Datasheet
Download NON Datasheet




Cooper NON
NON/NOS, 600/250Vac Class K5 & H
NON (250V) 18-600A, General Purpose Fuses
Description: Basic protection 250V NON Class K5 and H
general purpose, non-current-limiting, one-time fuses.
Catalog Symbol: NON-(amp)
Ratings:
Volts — 250Vac
— 125Vdc (18-100A)
Amps — 18-600A
IR — 50kA Vac RMS Sym. (18-60A)
— 10kA Vac RMS Sym. (65-600A)
— 50kA Vdc (18-60A)
— 10kA Vdc (65-100A)
Agency Information:
CE, UL Listed, Class K5 (18-60A), Std. 248-9,
Class H (65-600A), Std. 248-6 (125Vdc 18-100A),
UL Guide JDDZ, File E4274
CSA Certified, Class 1421-01, File 53787 (18-12A, 65-600A)
† For CSA Certified 15-60A, see PON Data Sheet # 4126.
Catalog Numbers (amps)
NON-18
NON-3
NON-12
NON-12
NON-3210 NON-15
NON-34
NON-4
NON-20
NON-810
NON-1
NON-5
NON-6
NON-25
NON-30
NON-114
NON-614
NON-35
NON-112
NON-7
NON-40
NON-1610 NON-8
NON-45
NON-2
NON-9
NON-50
NON-212
NON-10
NON-60
NON-65
NON-70
NON-75
NON-80
NON-90
NON-100
NON-110
NON-125
NON-150
NON-175
NON-200
NON-225
NON-250
NON-300
NON-350
NON-400
NON-450
NON-500
NON-600
Carton Quantity and Weight
Amp Rating
Carton Qty.
18-30
35–60
10
10
65–100
5
110–200
1
225–400
1
450–600
1
Dimensions – in
All Diameters ± 0.008
2"
(0.031)
0.56" (± 0.008)
1/8 to 30A
3"
(0.031)
450 to 600A
0.81" (± 0.008)
10.38" ( 0.094)
8.63" (± 0.094)
2.59"
2.06"
35 to 60A
225 to 400A
5.88" (± 0.062)
7.13" (± 0.062)
70 to 100A
1.06"
110 to 200A
1.56"
Features:
• Protect lighting, heating and other circuits not subject to temporary
surges and where available short-circuit currents are relatively low
• NON one-time fuses do not have any appreciable degree of time-
delay and thus should not be specified in circuits where large
transients or motor overloads occur. Use Bussmann advanced
protection FUSETRON™ FRN-R or ultimate protection Low-Peak™
LPN-RK dual-element, time-delay fuses.
• For general purpose circuits, size at amp rating of circuit
• For motor circuits, size at 300% to 400% according to the NEC®
motor ampacity tables 430.247 to 430.250, per 430.6(A)(1)
Recommended Fuse Blocks
Fuse Amps
0-30
1-Pole
H25030-1
35-60
H25060-1
70-100
HM25100-1CR
110-200
HM25200-1CR
225-400
HM25400-1CR
450-600
HM25600-1CR
2-Pole
H25030-2
H25060-2
HM25100-2CR
HM25200-2CR
HM25400-2CR
HM25600-2CR
3-Pole
H25030-3
H25060-3
HM25100-3CR
HM25200-3CR
HM25400-3CR
HM25600-3CR
For additional information on 250 volt fuse blocks, see Data
Sheet # 1112 (H250) and product brochure # 3192 (HM Se-
ries).
Fuse Reducers For Class R Fuses
Equipment
Desired Fuse
Fuse Clips
60A
(Case) Size
30A
100A
30A
60A
200A
60A
200A
100A
400A
100A
200A
Catalog Numbers
(Pairs) 250V
NO.263
NO.213
NO.216
NO.226
NO.2621
NO.2641
NO.2642
For additional information on Class K5 & H fuse reducers, see
Data Sheet # 1118.
0713
BU-SB13738
Page 1 of 4
Data Sheet # 1030



Cooper NON
NON/NOS, 600/250Vac Class K5 & H
NON (250V) 18-600A, General Purpose Fuses
Time-Current Curves - Average Melt
AMP RATING
300
100
10
1
0.1
0.01
0713
BU-SB13738
CURRENT IN AMPS
Page 2 of 4
Data Sheet # 1030



Cooper NON
NON/NOS, 600/250Vac Class K5 & H
NOS (600V), 1-600A, General Purpose Fuses
Description: Basic protection 600V NOS Class K5 and H
general purpose, non-current-limiting, one-time fuses.
Catalog Symbol: NOS-(amp)
Ratings:
Volts — 600Vac
Amps — 1-600A
IR — 50kA Vac RMS Sym. (1-60A)
— 10kA Vac RMS Sym. (70-600A)
Agency Information:
CE, UL Listed, Class K5 (1-60A), Std. 248-9,
Class H (70-600A), Std. 248-6, UL Guide JDDZ, File E4273
CSA Certified, Class 1421-01, File 53787
Catalog Numbers (amps)
NOS-1
NOS-9
NOS-40
NOS-2
NOS-10
NOS-45
NOS-3
NOS-12
NOS-50
NOS-4
NOS-15
NOS-60
NOS-5
NOS-20
NOS-70
NOS-6
NOS-25
NOS-75
NOS-7
NOS-30
NOS-80
NOS-8
NOS-35
NOS-90
NOS-100
NOS-110
NOS-125
NOS-150
NOS-175
NOS-200
NOS-225
NOS-250
NON-300
NOS-350
NOS-400
NOS-450
NOS-500
NOS-600
NOS 600V Carton Quantity and Weight
Amp Rating
Carton Qty.
1–30
10
35–60
10
70–100
5
110–200
1
225–400
1
450–600
1
Dimensions – in
All Diameters ± 0.008
5" (± 0.031)
0.81" (± 0.008)
1 to 30A
450 to 600A
5.5" (± 0.031)
13.38" ( 0.094)
11.63" (± 0.094)
35 to 60A
1.06" (± 0.008)
225 to 400A
3.13"
2.59"
7.9" (± 0.062)
9.63" (± 0.062)
70 to 100A
1.34"
110 to 200A
1.84"
Features:
• Protect lighting, heating and other circuits not subject to temporary
surges and where available short-circuit currents are relatively low
• NOS one-time fuses do not have any appreciable degree of time-
delay and thus should not be specified in circuits where large
transients or motor overloads occur. Use Bussmann advanced
protection FUSETRON™ LPS-R or ultimate protection Low-Peak™
LPS-RK dual-element, time-delay fuses.
• For general purpose circuits, size at amp rating of circuit
• For motor circuits, size at 300% to 400% according to the NEC®
motor ampacity tables 430.247 to 430.250, per 430.6(A)(1)
Recommended Fuse Blocks
Fuse Amps
1-Pole
0-30
H60030-1
35-60
H60060-1
70-100
HM60100-1CR
110-200
HM60200-1CR
225-400
HM60400-1CR
450-600
HM60600-1CR
2-Pole
H60030-2
H60060-2
HM60100-2CR
HM60200-2CR
HM60400-2CR
HM60600-2CR
3-Pole
H60030-3
H60060-3
HM60100-3CR
HM60200-3CR
HM60400-3CR
HM60600-3CR
For additional information on 600 volt fuse blocks, see Data
Sheet # 1112 (H) and product brochure # 3192 (HM Series).
Fuse Reducers For Class R Fuses
Equipment
Desired Fuse
Fuse Clips
60A
(Case) Size
30A
100A
30A
60A
200A
60A
200A
100A
400A
100A
200A
Catalog Numbers
(Pairs) 250V
NO.663
NO.216
NO.616
NO.626
NO.2621
NO.2641
NO.2642
For additional information on Class R fuse reducers, see
Data Sheet # 1118.
The only controlled copy of this Data Sheet is the electronic read-only version located on the Cooper Bussmann Network Drive. All other copies of this document are by definition uncontrolled. This bulletin is
intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Cooper Bussmann reserves the right, without notice, to change
design or construction of any products and to discontinue or limit distribution of any products. Cooper Bussmann also reserves the right to change or update, without notice, any technical information
contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.
0713
BU-SB13738
Page 3 of 4
Data Sheet # 1030







@ 2014 :: Datasheetspdf.com :: Semiconductors datasheet search & download site (Privacy Policy & Contact)