DatasheetsPDF.com

HO40-NP

LEM
Part Number HO40-NP
Manufacturer LEM
Description Current Transducer
Published Sep 20, 2019
Detailed Description Current Transducer HO-NP series IP N = 40, 60, 120, 150 A Ref: HO 40-NP, HO 60-NP, HO 120-NP, HO 150-NP For the elec...
Datasheet PDF File HO40-NP PDF File

HO40-NP
HO40-NP


Overview
Current Transducer HO-NP series IP N = 40, 60, 120, 150 A Ref: HO 40-NP, HO 60-NP, HO 120-NP, HO 150-NP For the electronic measurement of current: DC, AC, pulsed.
.
.
, with galvanic separation between the primary and the secondary circuit.
Features ●● Open loop multi-range current transducer ●● Voltage output ●● Single power supply +5 V ●● Overcurrent detect 2.
93 × IP N (peak value) ●● EEPROM Control ●● Galvanic separation between primary and secondary circuit ●● Low power consumption ●● Compact design for THT PCB mounting ●● Factory calibrated ●● Dedicated parameter settings available on request (see page 10).
Advantages ●● Low offset drift ●● Over-drivable Vref ●● 8 mm creepage /clearance ●● Fast response.
Applications ●● AC variable speed and servo motor drives ●● Static converters for DC motor drives ●● Battery supplied applications ●● Uninterruptible Power Supplies (UPS) ●● Switched Mode Power Supplies (SMPS) ●● Power supplies for welding applications ●● Combiner box ●● Solar inverter on DC side of the inverter (MPPT).
Standards ●● IEC 61800-1: 1997 ●● IEC 61800-2: 2015 ●● IEC 61800-3: 2004 ●● IEC 61800-5-1: 2007 ●● IEC 62109-1: 2010 ●● UL 508: 2013.
Application Domain ●● Industrial.
N°97.
K3.
23.
000.
0; N°97.
K3.
27.
000.
0; N°97.
K3.
36.
000.
0; N°97.
K3.
39.
000.
0; 97.
K3.
27.
006.
0; 97.
K3.
39.
006.
0.
19October2017/version 6 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice Page 1/13 www.
lem.
com HO 40 .
.
.
150-NP series Absolute maximum ratings Parameter Symbol Unit Value Supply voltage (not destructive) Supply voltage (not entering non standard modes) UC UC V V 8 6.
5 Primary conductor temperature TB °C 120 Electrostatic discharge voltage UESD kV 2 Stresses above these ratings may cause permanent damage.
Exposure to absolute maximum ratings for extended periods may degrade reliability.
UL 508: Ratings and assumptions of certification File # E189713 Volume: 2 Section: 5 Standards ●...