DatasheetsPDF.com

AP200-B10

LEM
Part Number AP200-B10
Manufacturer LEM
Description AC Current transducer AP-B10
Published Mar 26, 2005
Detailed Description AC Current transducer AP-B10 Split core transducer for the electronic measurement AC waveforms current, with galvanic is...
Datasheet PDF File AP200-B10 PDF File

AP200-B10
AP200-B10


Overview
AC Current transducer AP-B10 Split core transducer for the electronic measurement AC waveforms current, with galvanic isolation between the primary (High power) and the secondary circuits (Electronic circuit).
Switch selectable ranges and RMS 0-5V and 0-10V switch selectable voltage output.
IPN = 10 .
.
400 A Preliminary Electrical data Primary Nominal Current IPN (A.
t.
RMS) 10,25,50 50,75,100 100,150,200 200,300,400 RL VC Vd Analogue Output Signal VOUT (V) 0-5V or 0-10V 0-5V or 0-10V 0-5V or 0-10V 0-5V or 0-10V Type Features • RMS output • Split core type • 5V & 10V switch selectable voltage output.
• DIN mounting & Panel mounting • Eliminates insertion loss • Switch selectable ranges AP 50 B10 AP 100 B10 AP 200 B10 AP 400 B10 ≥ 10 kΩ +24 ±5% V DC 5 kV 18 V Load resistance Supply voltage R.
m.
s.
voltage for AC isolation test, 50/60Hz, 1 mn Limitation voltage output Advantages • Large aperture for cable up to Ø18mm • High isolation between primary and secondary circuits Accuracy-Dynamic performance data • Easy to mount < ±1 % of IPN < ±0.
5 % of IPN < ±0.
5 % of IPN ±1 mV/K ±0.
1 %/K < 500 ms 10 .
.
6000 Hz ε X L VOE VOT TC ε G tr f Accuracy @ IPN, TA = 25°C (without offset) Linearity (0 .
.
± IPN) Electrical offset voltage, TA = 25°C Thermal drift of VOE Thermal drift of the gain (% of reading) Response time @ 90% of IP Frequency bandwidth (-3 dB) Applications • Automation systems Analog current reading for remote monitoring (e.
g.
motor) and software alarms.
• Panelmeters Simple connection displays power consumption.
General data TA TS m Ambient operating temperature Ambient storage temperature Mass Protection type Reliable isolation according to EN50178, EN61010 Creepage distance EMC in accordance with EN50082-2 Plastic according to UL94V0, CTI 1 -20 .
.
+60 °C -20 .
.
+85 °C 90 g IP20 300 V AC > 5.
5 mm Notes : Installation and maintenance should be done with power supply disconnected.
030708/0 LEM Components www.
lem.
com Dimensions AP(R)-B10 (unit : mm, ...



Similar Datasheet


@ 2014 :: Datasheetspdf.com :: Semiconductors datasheet search & download site. (Privacy Policy & Contact)