MTL5521

ETC
Part Number MTL5521
Manufacturer ETC
Description FREQUENCY TO CURRENT CONVERTER AND TRIP AMPLIFIER
Published Jun 1, 2006
Detailed Description www.DataSheet4U.com Hazardous area Safe area MTL5521 FREQUENCY TO CURRENT CONVERTER AND TRIP AMPLIFIER NAMUR Sensor ...
Datasheet PDF File MTL5521 PDF File

MTL5521
MTL5521


Overview
www.
DataSheet4U.
com Hazardous area Safe area MTL5521 FREQUENCY TO CURRENT CONVERTER AND TRIP AMPLIFIER NAMUR Sensor The MTL5521 converts a frequency or rotational speed signal from a proximity detector located in the hazardous area into a 0/4–20mA current signal suitable for driving safe area loads.
A display located on the top indicates the frequency.
The analogue output provides either a 0–20mA or 4–20mA signal that is proportional to the rotational speed or frequency of the input.
A relay output is provided, with two configurable set points, allowing monitoring of the input frequency.
When the input frequency is within this window the relay is energised and a yellow LED is illuminated.
A start-up delay is triggered by a NO contact allowing the system to start up without creating false alarms.
Configuration settings are made by two push button switches located on the front of the unit allowing the following parameters to be displayed and configured: • • • • • • • Output current either 0–20mA or 4–20mA 0/4mA and 20mA frequency values Line fault detection: Off, wire-break and/or short circuit Upper and lower threshold values of the set point relay (including hysteresis) Start uptime delay 0 to 1000s Filter time constant Scaling factors 1 2 3 4 5 6 7 8 9 10 11 12 13 + Load V or I – Vs+ Vs– ** 14 15 16 Start up delay ** see 'Power supply' for options Terminal 5 6 7 8 9 10 11 12 13 15 16 Function Namur Sensor +ve Namur Sensor –ve Start up delay +ve Start up delay –ve 0/4–20mA output +ve Speed Monitor Speed Monitor Speed Monitor 0/4–20mA output –ve Supply +ve Supply –ve A line fault detect facility detects open and/or short circuits in the field.
When a fault is detected the relay de-energises and the yellow LED changes to red.
SPECIFICATION Number of channels One, with a configurable alarm Location of delay switch Zone 0, IIC, T6 hazardous area Div.
1, Group A hazardous location Location of proximity detector Zone 0, IIC, T4–6 hazardous area if suitably...