DatasheetsPDF.com

MP141x

M-System
Part Number MP141x
Manufacturer M-System
Description RTD Input Limit Alarm
Published Aug 26, 2008
Detailed Description INSTRUCTION MANUAL RTD INPUT LIMIT ALARM Thank you for choosing M-System. Before use, check specifications on the unit ...
Datasheet PDF File MP141x PDF File

MP141x
MP141x


Overview
INSTRUCTION MANUAL RTD INPUT LIMIT ALARM Thank you for choosing M-System.
Before use, check specifications on the unit label.
If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
model MP1400 through MP1423 Adjustments •Setpoint The MP1400 Series has five styles of setpoint adjustment: MP14X0 Top-accessed, 3-turn screw(s) MP14X2 Remote dial connection(s), 1k to 100k ohms MP14X3 DC-programmable, 0 to 1V The setpoint is adjustable over the entire input span.
A) Set deadband at its minimum (fully counterclockwise) before adjusting the setpoint.
B) With the specified trip Resistance/RTD input applied, adjust setpoint until the relay trips.
For Hi trip calibration, start with the setpoint above the desired trip.
For Lo trip calibration start below the desired trip.
•Deadband The deadband is independently adjustable for both setpoints in dual alarms.
A) Set deadband at its minimum (fully counterclockwise).
Set setpoint to desire...



Similar Datasheet


@ 2014 :: Datasheetspdf.com :: Semiconductors datasheet search & download site. (Privacy Policy & Contact)