DatasheetsPDF.com

DRP-480

Mean Well Enterprises
Part Number DRP-480
Manufacturer Mean Well Enterprises
Description 480W Single Output Industrial DIN RAIL
Published Jul 29, 2009
Detailed Description www.DataSheet4U.com 480W Single Output Industrial DIN RAIL with PFC Function Features : DRP-480 series Built-in passi...
Datasheet PDF File DRP-480 PDF File

DRP-480
DRP-480



Overview
www.
DataSheet4U.
com 480W Single Output Industrial DIN RAIL with PFC Function Features : DRP-480 series Built-in passive PFC function compliance to EN61000-3-2 High efficiency 89% and low dissipation Protections:Short circuit/Over load/Over voltage/Over temperature Cooling by free air convection Built-in constant current limiting circuit Can be installed on DIN rail TS-35/7.
5 or 15 UL 508(industrial control equipment)approved EN61000-6-2(EN50082-2) industrial immunity level 100% full load burn-in test 3 years warranty R SPECIFICATION MODEL DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER OUTPUT VOLTAGE ADJ.
RANGE DRP-480-24 24V 20A 0 ~ 20A 480W DRP-480-48 48V 10A 0 ~ 10A 480W 120mVp-p 48 ~ 53V 1.
0% 0.
5% 1.
0% RIPPLE & NOISE (max.
) Note.
2 120mVp-p 24 ~ 28V VOLTAGE TOLERANCE Note.
3 1.
0% LINE REGULATION LOAD REGULATION SETUP, RISE TIME HOLD TIME (Typ.
) VOLTAGE RANGE FREQUENCY RANGE POWER FACTOR (Typ.
) INPUT EFFICIENCY (Typ.
) AC CURRENT (Typ.
) INRUSH CURRENT (Typ.
) LEAKAGE CURRENT OVER LOAD PROTECTION OVER VOLTAGE OVER TEMPERATURE WORKING TEMP.
WORKING HUMIDITY ENVIRONMENT STORAGE TEMP.
, HUMIDITY TEMP.
COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE 0.
5% 1.
0% 1200ms, 40ms/230VAC at full load 16ms/230VAC at full load 180 ~ 264VAC 47 ~ 63Hz 0.
7 89% 4A/230VAC COLD START 40A/230VAC <3.
5mA / 240VAC 250 ~ 370VDC 105 ~ 150% rated output power Protection type : Constant current limiting, recovers automatically after fault condition is removed 54 ~ 60V 30 ~ 36V Protection type : Shut down o/p voltage, re-power on to recover 100 5 (TSW : Detect on heatsink of power switch) Protection type : Shut down o/p voltage, recovers automatically after temperature goes down -20 ~ +70 -20 ~ +85 (Refer to output load derating curve) , 10 ~ 95% RH 20 ~ 90% RH non-condensing 0.
03%/ (0 ~ 50 Component:10 ~ 500Hz, 2G 10min.
/1cycle, 60min.
each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 UL508, UL60950-1, TUV EN60950-1 Approved I/P-O/P:3KVAC I/P-FG:1.
5KVAC O/P-FG:0.
5KVAC...



Similar Datasheet


@ 2014 :: Datasheetspdf.com :: Semiconductors datasheet search & download site. (Privacy Policy & Contact)