DatasheetsPDF.com

V5013R1065

Honeywell
Part Number V5013R1065
Manufacturer Honeywell
Description INTERNAL THREADED END-CONNECTION LINEAR VALVE PN16
Published Jul 11, 2014
Detailed Description INTERNAL THREADED END-CONNECTION LINEAR VALVE PN16 PRODUCT DATA V5013R FEATURES       Brass body with internal t...
Datasheet PDF File V5013R1065 PDF File

V5013R1065
V5013R1065


Overview
INTERNAL THREADED END-CONNECTION LINEAR VALVE PN16 PRODUCT DATA V5013R FEATURES       Brass body with internal threaded end connections Low seat leakage rate Self-adjusting packing Accurate positioning to ensure state-of-the-art temperature control Directly-coupled electric and pneumatic actuators for easy mounting Constant total flow throughout full plug travel SPECIFICATIONS Action: Nominal pressure rating: Flow characteristic: Rangeability: Leakage rate: Stroke: Valve body: Pipe connections: Material: Dimensions: Trim: Seat: Plug: Stem: Packing: Stem up to close port A-AB PN16 equal percentage: port A-AB linear: port B-AB 50:1 0.
05% of kvs 20 mm Internal threading as per ISO228 Brass See Fig.
1 on page 3 DN15: stainless steel DN20.
.
.
50: body integrated Brass Stainless steel Spring-loaded carbon fiber reinforced PTFE V-rings APPLICATION Single seated control or shut-off valve for:  hot water;  chilled water;  saturated steam;  superheated steam;  domestic hot water; in heating, ventilation, air conditioning systems, and open circuits.
Operated by  electric linear actuators (e.
g.
ML6420/25, ML7420/25, ML6421, and ML7421) and  pneumatic actuators (e.
g.
, MP953).
Medium temperature and pressure: Water and steam 2 to 120 °C max.
1600 kPa 120 to 170 °C max.
1490 kPa Max.
temperature differential in alternating hot/cold 60 K water use: ® U.
S.
Registered Trademark Copyright © 2013 Honeywell Inc.
 All Rights Reserved EN0B-0065GE51 R0413 V5013R – PRODUCT DATA SIZES AND FLOW CAPACITIES Table 1.
Size and flow capacity (in m /h) order number V5013R1032 V5013R1040 V5013R1057 V5013R1065 V5013R1073 V5013R1081 V5013R1099 valve size DN15 DN15 DN20 DN25 DN32 DN40 DN50 kVS m3/h 2.
5 4 6.
3 10 16 25 40 3 INSTALLATION Water should meet VDI2035 requirements.
Do not install valve with stem below the horizontal.
Fluid flow must correspond with the arrow direction on the valve body.
The installation of a strainer is strongly recommended.
SPARE PARTS Repair packing...



Similar Datasheet


@ 2014 :: Datasheetspdf.com :: Semiconductors datasheet search & download site. (Privacy Policy & Contact)