DatasheetsPDF.com

FAN41501

Fairchild Semiconductor
Part Number FAN41501
Manufacturer Fairchild Semiconductor
Description Ground Fault Interrupter Self-Test Digital Controller
Published Feb 15, 2016
Detailed Description FAN41501 — Ground Fault Interrupter Self-Test Digital Controller June 2014 FAN41501 Ground Fault Interrupter Self-Test...
Datasheet PDF File FAN41501 PDF File

FAN41501
FAN41501


Overview
FAN41501 — Ground Fault Interrupter Self-Test Digital Controller June 2014 FAN41501 Ground Fault Interrupter Self-Test Digital Controller Features  Meets 2015 UL943 Self-Test GFCI Requirement  Internal 1-Second and 90-Minute Self-Test Timers  Periodic Functional Testing for Key GFIC Components: GFCI Controller, Solenoid, Sense Transformer, and Silicon-Controlled Rectifier (SCR)  Periodic EOL Testing without Compromising Normal GFCI Protection  Built-in Noise Filters Reduce False EOL Signals  Automatic EOL Reset Capability  Easily Added to Existing GFCI Applications  Built-in 5 V Shunt Regulator  Energy-Saving System Solution  Minimum External Components  Space-Saving SuperSOT™ 6-Pin Package Applications  GFCI Output Receptacle  GFCI Circuit Breakers  Portable GFCI Cords Description The FAN41501 is a digital controller for periodic functional testing of key Ground Fault Circuit Interrupters (GFCI) components.
In combination with an existing Fairchild GFI controller, it periodically tests for the functional operation of the GFCI controller, solenoid, sense transformer, SCR, and other discrete components without disrupting power to the load or compromising normal GFCI protection functionality.
If the FAN41501 detects a faulty GFCI component, it generates an End-of-Life (EOL) fault signal that can be used to deny power and/or automatically reset after the denial of power.
When the AC power is first applied, an internal timer starts a test cycle at one second.
After this initial test cycle, the internal timer starts a test cycle every 90 minutes.
During a test cycle, the FAN41501 simulates a ground fault and monitors the key GFCI components.
If the FAN41501 detects a component fault, it verifies the fault several times to prevent a false EOL signal.
At no time during a test cycle is the normal GFCI protection disabled or compromised.
The FAN41501 includes a 5 V shunt regulator, onesecond timer, 90-minute timer, digital control logic, detection comparato...