LEM
Part Number HAZ20000-SRU
Manufacturer LEM
Description (HAZ4000-SRU - HAZ20000-SRU) Current Transducers
Published Jun 2, 2007
Detailed Description Current Transducers HAZ 4000..20000-SRU For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvan...
Datasheet PDF File HAZ20000-SRU PDF File

HAZ20000-SRU
HAZ20000-SRU


Overview
Current Transducers HAZ 4000.
.
20000-SRU For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 4000.
.
20000 A VOUT = 0-10 V (T-RMS DC) Electrical data Primary nominal r.
m.
s.
current IPN (A) 4000 6000 10000 12000 14000 20000 Primary current measuring range IP (A) ± ± ± ± ± ± 4000 6000 10000 12000 14000 20000 Type HAZ 4000-SRU HAZ 6000-SRU HAZ 10000-SRU HAZ 12000-SRU HAZ 14000-SRU HAZ 20000-SRU Features • Hall effect measuring principle • Galvanic isolation between primary ± 15 ± 30 30,000 > 1000 0-10 100 > 10 V mA A MΩ V DC Ω kΩ www.
DataSheet4U.
com VC IC IOC RIS VOUT ROUT RL Supply voltage (± 5 %) Current consumption Overload capacity Isolation resistance @ 500 VDC Output voltage @ ± IPN, RL = 10 kΩ, TA = 25°C Output internal resistance approx.
Load resistance • True-rms, 0-10V DC voltage output • Isolation voltage 12kV Rms/ 50 Hz • Low power consumption • Package in PBT meeting UL 94-V0 / 1 min and secondary circuit Advantages • Easy mounting • Small size and space savings • Only one design for wide current • High immunity against external interference ratings range Accuracy - Dynamic performance data X ε L VOE VOH VOT TCε G tr f Accuracy @ IPN, TA = 25°C (without offset) Linearity error 1) (0 .
.
± IPN) Electrical offset voltage, TA = 25°C, @ IP = 0 Hysteresis offset voltage @ IP = 0; after an excursion of 1 x IPN Thermal drift of VOE Thermal drift of the gain (% of reading) Response time @ 90% of IPN Frequency range, ±3 dB, small signal 2) <±1 % < ± 0.
5 % of IPN < ± 100 mV < ± 12.
5 mV <±1 mV/K < ± 0.
05 %/K < 400 ms DC and 15 to 3kHz Applications • Battery supplied applications • Uninterruptible Power Supplies • Power supplies for welding and telecom applications.
(UPS) General data TA TS Ambient operating temperature Ambient storage temperature Housing PBT 30% glassfiber UL94 classification Mass Standards 3) - 25 .
.
+...